EA-250AC6-C09 C
17.80 kW
Defrost: Electric
Product code: EA-435AG8-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,040 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 67.8 m² |
| Inner volume | 25.7 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 124 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 660 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.0 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-435AG8-C01 C | None |
|---|---|
| EA-435AG8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.75 | 7.70 | 7.68 | 7.69 | 7.64 | 7.56 | 7.44 | 7.59 | 8.08 | 8.74 | 8.53 | 8.46 | 8.37 | 8.25 |
| 5 | 9.88 | 9.94 | 10.02 | 10.10 | 10.09 | 10.01 | 9.86 | 9.99 | 10.59 | 11.45 | 11.08 | 10.96 | 10.78 | 10.53 |
| 6 | 11.94 | 12.16 | 12.36 | 12.55 | 12.61 | 12.56 | 12.42 | 12.52 | 13.25 | 14.32 | 13.81 | 13.62 | 13.33 | 12.88 |
| 7 | 13.98 | 14.36 | 14.72 | 15.04 | 15.16 | 15.17 | 15.05 | 15.14 | 16.02 | 17.30 | 16.67 | 16.41 | 16.03 | 15.40 |
| 8 | 15.82 | 16.43 | 16.98 | 17.47 | 17.74 | 17.80 | 17.70 | 17.81 | 18.85 | 20.35 | 19.64 | 19.32 | 18.85 | 18.07 |
| 9 | 17.47 | 18.27 | 19.02 | 19.68 | 20.08 | 20.29 | 20.28 | 20.48 | 21.69 | 23.40 | 22.62 | 22.26 | 21.72 | 20.79 |
| 10 | 18.98 | 20.02 | 20.99 | 21.72 | 22.27 | 22.59 | 22.68 | 22.92 | 24.29 | 26.27 | 25.53 | 25.17 | 24.61 | 23.56 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 25.526 |
| SC2 | 0 | 8 | 17.813 |
| SC3 | -18 | 7 | 15.087 |
| SC4 | -25 | 6 | 12.364 |
| SC5 | -34 | 6 | 12.001 |
| A | 2357 mm |
|---|---|
| B | 673 mm |
| C | 525 mm |
| F | 495 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2357 mm |
|---|---|
| Width | 623 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.