EA-445AC8-C01 C
23.46 kW
Defrost: Electric
Product code: EA-440AE6-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 11,146 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 84.4 m² |
| Inner volume | 24.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 125 kg |
| Quantity | 4 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 640 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-440AE6-C01 C | None |
|---|---|
| EA-440AE6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.06 | 9.98 | 9.94 | 9.93 | 9.86 | 9.74 | 9.59 | 9.81 | 10.44 | 11.30 | 11.04 | 10.96 | 10.85 | 10.62 |
| 5 | 12.92 | 12.98 | 13.06 | 13.14 | 13.10 | 12.98 | 12.79 | 12.96 | 13.76 | 14.87 | 14.41 | 14.26 | 14.05 | 13.76 |
| 6 | 15.77 | 16.02 | 16.26 | 16.44 | 16.50 | 16.41 | 16.20 | 16.34 | 17.30 | 18.69 | 18.04 | 17.80 | 17.45 | 16.92 |
| 7 | 18.41 | 18.92 | 19.39 | 19.80 | 19.97 | 19.94 | 19.75 | 19.87 | 21.02 | 22.71 | 21.90 | 21.59 | 21.12 | 20.36 |
| 8 | 20.73 | 21.49 | 22.19 | 22.82 | 23.20 | 23.34 | 23.28 | 23.48 | 24.84 | 26.82 | 25.91 | 25.53 | 24.95 | 23.99 |
| 9 | 22.88 | 23.93 | 24.89 | 25.63 | 26.14 | 26.41 | 26.44 | 26.71 | 28.31 | 30.65 | 29.79 | 29.40 | 28.81 | 27.73 |
| 10 | 24.88 | 26.14 | 27.37 | 28.45 | 29.13 | 29.52 | 29.62 | 29.93 | 31.73 | 34.34 | 33.40 | 32.96 | 32.29 | 31.14 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 33.399 |
| SC2 | 0 | 8 | 23.475 |
| SC3 | -18 | 7 | 19.891 |
| SC4 | -25 | 6 | 16.258 |
| SC5 | -34 | 6 | 15.841 |
| A | 2567 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2235 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2567 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.