EA-450AC8-C09 C
30.13 kW
Defrost: Electric
Product code: EA-445AC4-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 19,955 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 106.5 m² |
| Inner volume | 23.5 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 149 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,960 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | E |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø54 |
| EA-445AC4-C01 C | None |
|---|---|
| EA-445AC4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.45 | 12.27 | 12.15 | 12.06 | 11.91 | 11.74 | 11.55 | 11.70 | 12.36 | 13.32 | 12.95 | 12.82 | 12.64 | 12.37 |
| 5 | 16.48 | 16.50 | 16.47 | 16.49 | 16.36 | 16.14 | 15.86 | 15.98 | 16.93 | 18.25 | 17.70 | 17.51 | 17.26 | 16.90 |
| 6 | 20.32 | 20.68 | 21.03 | 21.26 | 21.26 | 21.05 | 20.73 | 20.83 | 22.04 | 23.74 | 22.91 | 22.63 | 22.23 | 21.66 |
| 7 | 23.49 | 24.17 | 24.79 | 25.34 | 25.57 | 25.69 | 25.64 | 25.89 | 27.47 | 29.70 | 28.67 | 28.28 | 27.72 | 26.85 |
| 8 | 26.48 | 27.41 | 28.34 | 29.16 | 29.65 | 29.88 | 29.89 | 30.16 | 31.99 | 34.66 | 33.73 | 33.36 | 32.83 | 31.96 |
| 9 | 29.14 | 30.59 | 31.89 | 33.02 | 33.74 | 34.11 | 34.20 | 34.52 | 36.61 | 39.68 | 38.60 | 38.16 | 37.51 | 36.45 |
| 10 | 31.70 | 33.60 | 35.32 | 36.81 | 37.79 | 38.33 | 38.54 | 38.93 | 41.30 | 44.75 | 43.57 | 43.06 | 42.31 | 41.06 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 43.574 |
| SC2 | 0 | 8 | 30.161 |
| SC3 | -18 | 7 | 25.489 |
| SC4 | -25 | 6 | 21.033 |
| SC5 | -34 | 6 | 20.420 |
| A | 3167 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2835 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø54 |
| Length | 3167 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.