EA-345AG8-C01 C
27.50 kW
Defrost: None
Product code: EA-445AC6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 21,002 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 76.7 m² |
| Inner volume | 23.5 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 143 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,960 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø54 |
| EA-445AC6-C01 C | None |
|---|---|
| EA-445AC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.19 | 10.96 | 10.80 | 10.67 | 10.51 | 10.32 | 10.13 | 10.20 | 10.76 | 11.57 | 11.21 | 11.08 | 10.90 | 10.63 |
| 5 | 14.84 | 14.77 | 14.73 | 14.69 | 14.54 | 14.32 | 14.05 | 14.11 | 14.93 | 16.07 | 15.55 | 15.37 | 15.12 | 14.70 |
| 6 | 18.50 | 18.69 | 18.86 | 18.99 | 18.92 | 18.74 | 18.46 | 18.50 | 19.56 | 21.05 | 20.31 | 20.05 | 19.69 | 19.16 |
| 7 | 21.71 | 22.20 | 22.68 | 23.13 | 23.38 | 23.42 | 23.18 | 23.22 | 24.55 | 26.45 | 25.53 | 25.19 | 24.67 | 23.89 |
| 8 | 24.56 | 25.36 | 26.10 | 26.68 | 27.09 | 27.29 | 27.33 | 27.56 | 29.24 | 31.69 | 30.88 | 30.56 | 30.06 | 29.09 |
| 9 | 27.24 | 28.27 | 29.31 | 30.25 | 30.84 | 31.18 | 31.30 | 31.57 | 33.50 | 36.33 | 35.41 | 35.04 | 34.49 | 33.59 |
| 10 | 29.63 | 31.15 | 32.53 | 33.76 | 34.58 | 35.07 | 35.29 | 35.63 | 37.82 | 41.02 | 40.03 | 39.60 | 38.97 | 37.92 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 40.026 |
| SC2 | 0 | 8 | 27.563 |
| SC3 | -18 | 7 | 23.250 |
| SC4 | -25 | 6 | 18.860 |
| SC5 | -34 | 6 | 18.572 |
| A | 3167 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2835 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø54 |
| Length | 3167 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.