EA-440AG6-C01 C
25.47 kW
Defrost: Electric
Product code: EA-445AC7-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 21,371 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 66.8 m² |
| Inner volume | 23.5 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 141 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,960 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø54 |
| EA-445AC7-C01 C | None |
|---|---|
| EA-445AC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.16 | 9.89 | 9.69 | 9.53 | 9.35 | 9.16 | 8.97 | 8.98 | 9.47 | 10.17 | 9.84 | 9.72 | 9.55 | 9.31 |
| 5 | 13.62 | 13.46 | 13.34 | 13.24 | 13.05 | 12.81 | 12.53 | 12.55 | 13.26 | 14.24 | 13.75 | 13.58 | 13.32 | 12.93 |
| 6 | 17.12 | 17.16 | 17.18 | 17.22 | 17.12 | 16.89 | 16.59 | 16.58 | 17.51 | 18.82 | 18.12 | 17.88 | 17.54 | 17.05 |
| 7 | 20.39 | 20.74 | 21.09 | 21.35 | 21.39 | 21.23 | 20.96 | 20.96 | 22.14 | 23.81 | 22.91 | 22.58 | 22.11 | 21.38 |
| 8 | 23.15 | 23.76 | 24.35 | 24.89 | 25.21 | 25.30 | 25.31 | 25.50 | 26.98 | 29.08 | 28.07 | 27.68 | 27.10 | 26.19 |
| 9 | 25.76 | 26.69 | 27.44 | 28.21 | 28.70 | 28.96 | 29.03 | 29.26 | 31.03 | 33.63 | 32.77 | 32.42 | 31.90 | 31.06 |
| 10 | 28.20 | 29.36 | 30.52 | 31.56 | 32.23 | 32.63 | 32.79 | 33.07 | 35.08 | 38.03 | 37.10 | 36.70 | 36.11 | 35.14 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 37.096 |
| SC2 | 0 | 8 | 25.495 |
| SC3 | -18 | 7 | 21.388 |
| SC4 | -25 | 6 | 17.178 |
| SC5 | -34 | 6 | 17.155 |
| A | 3167 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2835 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø54 |
| Length | 3167 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.