EA-463ED10-C06 C
41.15 kW
Defrost: None
Product code: EA-450AE8-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 26,012 m³/h |
|---|---|
| Air throw | 21 m |
| External surface | 115.2 m² |
| Inner volume | 44.7 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 212 kg |
| Quantity | 4 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 2,840 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 84.0 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø54 |
| EA-450AE8-C09 C | None |
|---|---|
| EA-450AE8-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 17.00 | 16.74 | 16.56 | 16.43 | 16.21 | 15.94 | 15.63 | 15.79 | 16.69 | 17.94 | 17.36 | 17.15 | 16.85 | 16.40 |
| 5 | 22.22 | 22.23 | 22.27 | 22.31 | 22.16 | 21.88 | 21.50 | 21.62 | 22.89 | 24.65 | 23.84 | 23.57 | 23.17 | 22.59 |
| 6 | 27.42 | 27.80 | 28.16 | 28.41 | 28.45 | 28.26 | 27.89 | 27.99 | 29.61 | 31.89 | 30.76 | 30.35 | 29.77 | 28.89 |
| 7 | 32.24 | 33.08 | 33.91 | 34.60 | 34.90 | 34.88 | 34.57 | 34.69 | 36.69 | 39.59 | 38.22 | 37.69 | 36.91 | 35.67 |
| 8 | 36.35 | 37.66 | 38.88 | 39.98 | 40.67 | 40.93 | 41.02 | 41.39 | 43.91 | 47.51 | 45.98 | 45.36 | 44.43 | 42.92 |
| 9 | 40.21 | 42.04 | 43.53 | 45.03 | 46.02 | 46.57 | 46.79 | 47.25 | 50.14 | 54.36 | 53.01 | 52.43 | 51.55 | 50.08 |
| 10 | 43.79 | 45.99 | 48.17 | 50.11 | 51.39 | 52.20 | 52.57 | 53.16 | 56.42 | 61.19 | 59.72 | 59.07 | 58.08 | 56.39 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 59.724 |
| SC2 | 0 | 8 | 41.392 |
| SC3 | -18 | 7 | 34.758 |
| SC4 | -25 | 6 | 28.155 |
| SC5 | -34 | 6 | 27.543 |
| A | 3787 mm |
|---|---|
| B | 640 mm |
| C | 715 mm |
| F | 560 mm |
| E1 | 868 mm |
| E2 | 850 mm |
| E | 3435 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø54 |
| Length | 3787 mm |
|---|---|
| Width | 640 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.