EA-191AE4-C04 C
53.22 kW
Defrost: None
Product code: EA-463ED4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 31,434 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 333.5 m² |
| Inner volume | 64.4 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 382 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 2,400 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 80.5 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-463ED4-C01 C | None |
|---|---|
| EA-463ED4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 22.86 | 22.96 | 23.03 | 23.18 | 23.16 | 23.03 | 22.83 | 23.22 | 24.69 | 26.74 | 26.15 | 25.94 | 25.61 | 25.11 |
| 5 | 28.87 | 29.46 | 29.96 | 30.37 | 30.48 | 30.37 | 30.08 | 30.42 | 32.29 | 34.89 | 33.96 | 33.64 | 33.19 | 32.54 |
| 6 | 34.56 | 35.60 | 36.66 | 37.53 | 37.94 | 38.00 | 37.78 | 38.10 | 40.39 | 43.67 | 42.38 | 41.89 | 41.20 | 40.14 |
| 7 | 39.35 | 41.16 | 42.79 | 44.21 | 45.10 | 45.57 | 45.70 | 46.17 | 48.94 | 52.94 | 51.36 | 50.75 | 49.83 | 48.37 |
| 8 | 43.75 | 46.25 | 48.50 | 50.44 | 51.71 | 52.42 | 52.70 | 53.28 | 56.56 | 61.38 | 59.84 | 59.22 | 58.29 | 56.75 |
| 9 | 47.78 | 51.03 | 53.97 | 56.52 | 58.24 | 59.24 | 59.71 | 60.41 | 64.14 | 69.59 | 67.89 | 67.16 | 66.06 | 64.22 |
| 10 | ≈ 51.44 | 55.51 | 59.21 | 62.42 | 64.62 | 66.03 | 66.73 | 67.60 | 71.78 | 77.88 | 76.04 | 75.21 | 73.96 | 71.82 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 76.039 |
| SC2 | 0 | 8 | 53.278 |
| SC3 | -18 | 7 | 44.621 |
| SC4 | -25 | 6 | 36.660 |
| SC5 | -34 | 6 | 34.874 |
| A | 3615 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 3235 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 3615 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.