Skip to Content

Unit cooler EA-550AC4-C10 C

Unit cooler EA-550AC4-C10 C
Illustrative photo

Producer: Karyer · Line: EA (General)

Product code: EA-550AC4-C10 C

Cooling capacity i
53.13 kW
Air flow
33,284 m³/h
Fin spacing
4.2 mm
Air throw
23 m
Fans
5 × ⌀500 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Data

Evaporator
Air flow 33,284 m³/h
Air throw 23 m
External surface 162.3 m²
Inner volume 35.3 dm³
Fin spacing 4.2 mm
Fin materialAluminium
Net weight 220 kg
Fans
Quantity 5
Diameter 500 mm
Speed 1,360 rpm
Power 3,450 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 64.0 dB(A)
Sound power 87.0 dB(A)
Energy class D
Connections
Inlet Ø35
Outlet Ø54
Defrost
EA-550AC4-C10 C None
EA-550AC4-C10 C ED Electric

Performance

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
53.132 kW
Low speed (Y)
46.157 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 21.09 22.11 22.99 23.73 24.18 24.25 24.05 24.46 25.92 28.03 27.31 27.04 26.60 25.92
5 25.48 27.13 28.37 29.63 30.47 30.98 31.19 31.80 33.85 36.79 36.05 35.78 35.38 34.75
6 28.83 31.46 33.59 35.47 36.80 37.66 38.10 38.86 41.36 44.99 44.10 43.74 43.20 42.33
7 ≈ 32.57 35.62 38.50 41.07 42.98 44.29 45.04 45.99 48.98 53.35 52.30 51.86 51.18 50.04
8 ≈ 33.79 ≈ 39.41 43.07 46.40 48.96 50.79 51.93 53.13 56.63 61.76 60.61 60.11 59.31 57.92
9 ≈ 20.32 ≈ 42.83 47.30 51.43 54.71 57.14 58.72 60.25 64.27 70.16 69.01 68.44 67.55 65.93
10 ≈ 12.52 ≈ 45.91 51.18 56.16 60.17 63.25 65.36 67.30 71.86 78.54 77.43 76.83 75.86 74.04

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 18.85 19.53 20.10 20.55 20.68 20.66 20.48 20.91 22.24 24.08 23.49 23.30 23.03 22.48
5 23.19 24.40 25.47 26.40 26.85 27.18 27.28 27.82 29.61 32.19 31.43 31.11 30.66 29.98
6 26.90 28.49 30.09 31.49 32.44 33.00 33.25 33.86 36.02 39.16 38.29 37.95 37.44 36.63
7 29.73 32.41 34.62 36.56 37.94 38.82 39.27 39.99 42.54 46.28 45.24 44.82 44.17 43.08
8 ≈ 32.99 36.03 38.89 41.44 43.31 44.58 45.29 46.16 49.12 53.47 52.32 51.82 51.04 49.66
9 ≈ 35.63 39.34 42.89 46.09 48.53 50.20 51.23 52.33 55.72 60.68 59.49 58.91 58.00 56.37
10 ≈ 26.83 ≈ 42.35 46.60 50.50 53.51 55.70 57.11 58.49 62.32 67.91 66.70 66.07 65.04 63.17

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 77.43166.695
SC2 0 8 53.13246.157
SC3 -18 7 41.91137.176
SC4 -25 6 33.58930.091
SC5 -34 6 29.66227.318

Dimensions

Dimension drawing of EA-550AC4-C10 C
Dimension drawing
Dimensions as drawn
A 4387 mm
B 590 mm
C 715 mm
F 510 mm
E1 818 mm
E2 800 mm
E 4035 mm
D IN 1 x Ø35
D OUT 1 x Ø54
Overall [mm]
Length 4387 mm
Width 590 mm
Height 715 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.