EA-563FE4-C08 C
120.15 kW
Defrost: None
Product code: EA-463GG7-C13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 69,216 m³/h |
|---|---|
| Air throw | 48 m |
| External surface | 585.9 m² |
| Inner volume | 170.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 735 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 70.0 dB(A) |
|---|---|
| Sound power | 93.7 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø66,7 |
| EA-463GG7-C13 C | None |
|---|---|
| EA-463GG7-C13 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 51.45 | 51.40 | 51.47 | 51.60 | 51.42 | 51.04 | 50.54 | 50.77 | 53.80 | 58.10 | 56.57 | 55.98 | 55.15 | 53.88 |
| 5 | 65.56 | 66.40 | 67.17 | 67.85 | 67.96 | 67.61 | 67.06 | 67.22 | 71.18 | 76.83 | 74.64 | 73.84 | 72.71 | 70.99 |
| 6 | 78.73 | 80.90 | 82.80 | 84.05 | 84.80 | 84.90 | 84.51 | 84.70 | 89.68 | 96.80 | 93.98 | 92.90 | 91.35 | 88.91 |
| 7 | 90.97 | 94.18 | 97.44 | 100.27 | 101.88 | 102.57 | 102.54 | 102.89 | 108.98 | 117.80 | 114.44 | 113.12 | 111.16 | 107.99 |
| 8 | 101.02 | 106.03 | 110.60 | 114.62 | 117.30 | 118.95 | 119.78 | 120.82 | 128.25 | 139.14 | 135.56 | 134.04 | 131.74 | 127.96 |
| 9 | 110.58 | 117.25 | 123.28 | 128.56 | 132.21 | 134.49 | 135.79 | 137.14 | 145.62 | 158.03 | 154.55 | 153.08 | 150.85 | 147.11 |
| 10 | 119.37 | 127.77 | 135.41 | 142.13 | 146.82 | 149.94 | 151.79 | 153.53 | 163.09 | 177.06 | 173.33 | 171.70 | 169.21 | 164.96 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 44.35 | 44.03 | 43.94 | 43.99 | 43.82 | 43.51 | 43.09 | 43.61 | 46.28 | 50.07 | 48.88 | 48.46 | 47.87 | 46.93 |
| 5 | 56.51 | 56.68 | 56.86 | 57.25 | 57.23 | 56.92 | 56.38 | 56.79 | 60.20 | 65.08 | 63.29 | 62.65 | 61.75 | 60.41 |
| 6 | 68.11 | 69.14 | 70.12 | 71.02 | 71.29 | 71.04 | 70.48 | 70.80 | 74.98 | 81.00 | 78.59 | 77.68 | 76.36 | 74.31 |
| 7 | 79.13 | 81.25 | 83.16 | 84.80 | 85.33 | 85.45 | 85.02 | 85.32 | 90.33 | 97.58 | 94.58 | 93.42 | 91.69 | 88.89 |
| 8 | 89.43 | 92.41 | 95.42 | 98.02 | 99.49 | 100.06 | 99.84 | 100.26 | 106.15 | 114.75 | 111.29 | 109.88 | 107.77 | 104.30 |
| 9 | 98.19 | 102.68 | 106.79 | 110.44 | 112.74 | 114.09 | 114.60 | 115.40 | 122.24 | 132.18 | 128.36 | 126.73 | 124.28 | 120.18 |
| 10 | 106.48 | 112.34 | 117.66 | 122.32 | 125.37 | 127.23 | 128.06 | 129.25 | 137.11 | 148.58 | 144.98 | 143.37 | 140.94 | 136.35 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 173.325 | 144.976 |
| SC2 | 0 | 8 | 120.815 | 100.255 |
| SC3 | -18 | 7 | 101.039 | 84.932 |
| SC4 | -25 | 6 | 82.801 | 70.117 |
| SC5 | -34 | 6 | 79.312 | 68.424 |
| A | 5615 mm |
|---|---|
| B | 1100 mm |
| C | 1185 mm |
| F | 1060 mm |
| G | 1130 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 5235 mm |
| D IN | 2 x Ø35 |
| D OUT | 2 x Ø66,7 |
| Length | 5615 mm |
|---|---|
| Width | 1210 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.