EA-163EE7-C01 C
12.20 kW
Defrost: None
Product code: EA-530AC4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,070 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 52.0 m² |
| Inner volume | 11.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 73 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 310 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 71.8 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| EA-530AC4-C01 C | None |
|---|---|
| EA-530AC4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.05 | 5.19 | 5.31 | 5.41 | 5.45 | 5.44 | 5.40 | 5.50 | 5.85 | 6.33 | 6.19 | 6.14 | 6.07 | 5.97 |
| 5 | 6.32 | 6.61 | 6.86 | 7.06 | 7.18 | 7.21 | 7.18 | 7.28 | 7.73 | 8.37 | 8.14 | 8.06 | 7.93 | 7.74 |
| 6 | 7.40 | 7.81 | 8.19 | 8.47 | 8.69 | 8.82 | 8.88 | 9.02 | 9.59 | 10.42 | 10.18 | 10.09 | 9.94 | 9.67 |
| 7 | 8.35 | 8.84 | 9.38 | 9.84 | 10.16 | 10.36 | 10.46 | 10.62 | 11.29 | 12.28 | 12.00 | 11.88 | 11.70 | 11.40 |
| 8 | 9.21 | 9.89 | 10.56 | 11.17 | 11.60 | 11.88 | 12.04 | 12.24 | 13.01 | 14.15 | 13.84 | 13.70 | 13.48 | 13.11 |
| 9 | ≈ 9.92 | 10.83 | 11.68 | 12.44 | 13.00 | 13.38 | 13.61 | 13.86 | 14.74 | 16.03 | 15.70 | 15.54 | 15.29 | 14.85 |
| 10 | ≈ 10.61 | 11.69 | 12.72 | 13.66 | 14.36 | 14.86 | 15.17 | 15.48 | 16.47 | 17.93 | 17.58 | 17.40 | 17.12 | 16.62 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 17.575 |
| SC2 | 0 | 8 | 12.237 |
| SC3 | -18 | 7 | 9.984 |
| SC4 | -25 | 6 | 8.191 |
| SC5 | -34 | 6 | 7.495 |
| A | 2407 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 428 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 2407 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.