EA-150AC4-C10 C
10.62 kW
Defrost: Electric
Product code: EA-530AC6-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,388 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 37.4 m² |
| Inner volume | 11.0 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 70 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 310 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 71.2 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-530AC6-C01 C | None |
|---|---|
| EA-530AC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.37 | 4.42 | 4.48 | 4.52 | 4.53 | 4.50 | 4.46 | 4.52 | 4.81 | 5.20 | 5.07 | 5.03 | 4.96 | 4.84 |
| 5 | 5.56 | 5.72 | 5.86 | 5.97 | 6.03 | 6.03 | 5.99 | 6.06 | 6.43 | 6.96 | 6.76 | 6.69 | 6.59 | 6.45 |
| 6 | 6.65 | 6.93 | 7.19 | 7.42 | 7.57 | 7.63 | 7.61 | 7.69 | 8.16 | 8.83 | 8.57 | 8.48 | 8.34 | 8.12 |
| 7 | 7.57 | 7.98 | 8.35 | 8.64 | 8.87 | 9.01 | 9.08 | 9.21 | 9.79 | 10.64 | 10.41 | 10.31 | 10.17 | 9.91 |
| 8 | 8.41 | 8.97 | 9.41 | 9.85 | 10.17 | 10.38 | 10.49 | 10.65 | 11.32 | 12.31 | 12.04 | 11.93 | 11.76 | 11.47 |
| 9 | 9.18 | 9.82 | 10.46 | 11.03 | 11.44 | 11.72 | 11.89 | 12.09 | 12.86 | 13.98 | 13.70 | 13.57 | 13.38 | 13.04 |
| 10 | ≈ 9.83 | 10.67 | 11.46 | 12.16 | 12.69 | 13.06 | 13.29 | 13.53 | 14.40 | 15.67 | 15.37 | 15.23 | 15.02 | 14.63 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 15.374 |
| SC2 | 0 | 8 | 10.645 |
| SC3 | -18 | 7 | 8.743 |
| SC4 | -25 | 6 | 7.190 |
| SC5 | -34 | 6 | 6.717 |
| A | 2407 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 428 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2407 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.