EA-630BC8-C05 C
9.46 kW
Defrost: None
Product code: EA-530AC7-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,745 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 32.6 m² |
| Inner volume | 11.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 53 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-530AC7-C05 C | None |
|---|---|
| EA-530AC7-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.89 | 3.91 | 3.93 | 3.95 | 3.94 | 3.91 | 3.86 | 3.92 | 4.17 | 4.51 | 4.40 | 4.36 | 4.30 | 4.20 |
| 5 | 4.95 | 5.05 | 5.15 | 5.23 | 5.25 | 5.24 | 5.19 | 5.25 | 5.57 | 6.02 | 5.84 | 5.78 | 5.70 | 5.58 |
| 6 | 6.00 | 6.20 | 6.38 | 6.53 | 6.60 | 6.63 | 6.59 | 6.66 | 7.06 | 7.63 | 7.40 | 7.31 | 7.18 | 6.97 |
| 7 | 6.93 | 7.23 | 7.51 | 7.77 | 7.93 | 8.03 | 8.04 | 8.10 | 8.59 | 9.31 | 9.03 | 8.93 | 8.76 | 8.48 |
| 8 | 7.74 | 8.16 | 8.55 | 8.85 | 9.09 | 9.23 | 9.30 | 9.42 | 10.01 | 10.88 | 10.62 | 10.51 | 10.34 | 10.04 |
| 9 | 8.49 | 9.04 | 9.49 | 9.93 | 10.24 | 10.44 | 10.55 | 10.71 | 11.38 | 12.36 | 12.08 | 11.95 | 11.75 | 11.40 |
| 10 | 9.17 | 9.80 | 10.43 | 10.98 | 11.38 | 11.65 | 11.80 | 11.99 | 12.75 | 13.85 | 13.56 | 13.41 | 13.18 | 12.78 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.556 |
| SC2 | 0 | 8 | 9.424 |
| SC3 | -18 | 7 | 7.842 |
| SC4 | -25 | 6 | 6.380 |
| SC5 | -34 | 6 | 6.051 |
| A | 2407 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 427.5 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2407 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.