EA-163EE10-C06 C
11.15 kW
Defrost: Electric
Product code: EA-530AE10-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,138 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 35.8 m² |
| Inner volume | 16.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 83 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 310 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 71.7 dB(A) |
| Energy class | A |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-530AE10-C01 C | None |
|---|---|
| EA-530AE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.59 | 4.66 | 4.72 | 4.78 | 4.80 | 4.78 | 4.73 | 4.80 | 5.10 | 5.52 | 5.38 | 5.33 | 5.26 | 5.17 |
| 5 | 5.76 | 5.93 | 6.10 | 6.24 | 6.31 | 6.33 | 6.30 | 6.37 | 6.76 | 7.32 | 7.10 | 7.03 | 6.92 | 6.74 |
| 6 | 6.90 | 7.20 | 7.47 | 7.71 | 7.83 | 7.90 | 7.91 | 7.99 | 8.48 | 9.19 | 8.93 | 8.83 | 8.67 | 8.42 |
| 7 | 7.91 | 8.35 | 8.74 | 9.10 | 9.34 | 9.50 | 9.54 | 9.62 | 10.22 | 11.09 | 10.80 | 10.68 | 10.49 | 10.17 |
| 8 | 8.80 | 9.37 | 9.90 | 10.37 | 10.65 | 10.86 | 10.99 | 11.16 | 11.87 | 12.90 | 12.63 | 12.50 | 12.31 | 11.96 |
| 9 | 9.60 | 10.32 | 10.92 | 11.51 | 11.95 | 12.25 | 12.42 | 12.64 | 13.44 | 14.62 | 14.33 | 14.19 | 13.97 | 13.58 |
| 10 | ≈ 10.33 | 11.09 | 11.95 | 12.68 | 13.22 | 13.61 | 13.85 | 14.12 | 15.02 | 16.34 | 16.04 | 15.88 | 15.64 | 15.20 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.039 |
| SC2 | 0 | 8 | 11.163 |
| SC3 | -18 | 7 | 9.208 |
| SC4 | -25 | 6 | 7.467 |
| SC5 | -34 | 6 | 6.971 |
| A | 2407 mm |
|---|---|
| B | 573 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 428 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2407 mm |
|---|---|
| Width | 573 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.