EA-340AC8-C01 C
12.17 kW
Defrost: None
Product code: EA-530AE4-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,525 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 77.6 m² |
| Inner volume | 15.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 72 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-530AE4-C05 C | None |
|---|---|
| EA-530AE4-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.37 | 5.41 | 5.47 | 5.52 | 5.53 | 5.51 | 5.45 | 5.57 | 5.93 | 6.44 | 6.29 | 6.24 | 6.17 | 6.08 |
| 5 | 6.69 | 6.83 | 6.96 | 7.08 | 7.13 | 7.12 | 7.05 | 7.15 | 7.58 | 8.22 | 7.97 | 7.88 | 7.74 | 7.54 |
| 6 | 8.00 | 8.25 | 8.48 | 8.66 | 8.76 | 8.77 | 8.71 | 8.79 | 9.31 | 10.08 | 9.75 | 9.61 | 9.41 | 9.09 |
| 7 | 9.18 | 9.58 | 9.93 | 10.24 | 10.41 | 10.46 | 10.40 | 10.48 | 11.10 | 12.00 | 11.61 | 11.44 | 11.18 | 10.75 |
| 8 | 10.23 | 10.76 | 11.24 | 11.66 | 11.93 | 12.01 | 12.03 | 12.15 | 12.88 | 13.93 | 13.49 | 13.28 | 12.98 | 12.45 |
| 9 | 11.19 | 11.88 | 12.43 | 12.99 | 13.35 | 13.53 | 13.58 | 13.72 | 14.54 | 15.73 | 15.29 | 15.08 | 14.75 | 14.19 |
| 10 | 12.07 | 12.94 | 13.64 | 14.32 | 14.77 | 15.04 | 15.13 | 15.30 | 16.22 | 17.54 | 17.06 | 16.82 | 16.45 | 15.81 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 17.055 |
| SC2 | 0 | 8 | 12.154 |
| SC3 | -18 | 7 | 10.321 |
| SC4 | -25 | 6 | 8.478 |
| SC5 | -34 | 6 | 8.063 |
| A | 2407 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 427.5 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 2407 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.