EA-240AE8-C01 C
10.47 kW
Defrost: None
Product code: EA-530AE8-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,116 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 43.4 m² |
| Inner volume | 16.3 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 69 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| EA-530AE8-C05 C | None |
|---|---|
| EA-530AE8-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.40 | 4.45 | 4.51 | 4.56 | 4.57 | 4.54 | 4.49 | 4.60 | 4.90 | 5.31 | 5.18 | 5.14 | 5.09 | 5.02 |
| 5 | 5.51 | 5.66 | 5.80 | 5.92 | 5.98 | 5.97 | 5.92 | 6.02 | 6.39 | 6.92 | 6.72 | 6.64 | 6.53 | 6.37 |
| 6 | 6.61 | 6.87 | 7.11 | 7.29 | 7.41 | 7.44 | 7.41 | 7.50 | 7.95 | 8.62 | 8.34 | 8.23 | 8.07 | 7.80 |
| 7 | 7.59 | 7.99 | 8.34 | 8.66 | 8.85 | 8.93 | 8.92 | 9.02 | 9.56 | 10.36 | 10.04 | 9.91 | 9.70 | 9.35 |
| 8 | 8.47 | 8.99 | 9.46 | 9.88 | 10.15 | 10.28 | 10.34 | 10.50 | 11.15 | 12.10 | 11.75 | 11.59 | 11.35 | 10.94 |
| 9 | 9.26 | 9.92 | 10.52 | 10.99 | 11.36 | 11.59 | 11.69 | 11.88 | 12.61 | 13.68 | 13.35 | 13.19 | 12.94 | 12.52 |
| 10 | 9.97 | 10.78 | 11.46 | 12.10 | 12.58 | 12.88 | 13.03 | 13.26 | 14.08 | 15.28 | 14.93 | 14.75 | 14.47 | 14.00 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 14.926 |
| SC2 | 0 | 8 | 10.499 |
| SC3 | -18 | 7 | 8.745 |
| SC4 | -25 | 6 | 7.105 |
| SC5 | -34 | 6 | 6.674 |
| A | 2407 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 427.5 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 2407 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.