EA-163FE7-C08 C
18.93 kW
Defrost: None
Product code: EA-535AE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 11,470 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 52.4 m² |
| Inner volume | 24.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 120 kg |
| Quantity | 5 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 825 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 77.0 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-535AE10-C01 C | None |
|---|---|
| EA-535AE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.90 | 7.81 | 7.76 | 7.73 | 7.65 | 7.54 | 7.40 | 7.52 | 7.98 | 8.61 | 8.36 | 8.26 | 8.12 | 7.91 |
| 5 | 10.23 | 10.25 | 10.30 | 10.35 | 10.32 | 10.21 | 10.06 | 10.15 | 10.76 | 11.61 | 11.23 | 11.10 | 10.93 | 10.69 |
| 6 | 12.54 | 12.67 | 12.86 | 13.04 | 13.09 | 13.03 | 12.89 | 12.97 | 13.73 | 14.82 | 14.31 | 14.12 | 13.84 | 13.42 |
| 7 | 14.69 | 15.07 | 15.44 | 15.76 | 15.90 | 15.92 | 15.81 | 15.90 | 16.83 | 18.18 | 17.57 | 17.32 | 16.96 | 16.38 |
| 8 | 16.66 | 17.26 | 17.83 | 18.35 | 18.69 | 18.84 | 18.79 | 18.90 | 20.02 | 21.64 | 20.94 | 20.65 | 20.23 | 19.51 |
| 9 | 18.42 | 19.25 | 20.02 | 20.71 | 21.08 | 21.36 | 21.46 | 21.71 | 23.04 | 24.98 | 24.36 | 24.05 | 23.56 | 22.72 |
| 10 | 20.06 | 21.14 | 22.04 | 22.91 | 23.51 | 23.89 | 24.06 | 24.36 | 25.86 | 28.04 | 27.37 | 27.06 | 26.59 | 25.77 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 27.374 |
| SC2 | 0 | 8 | 18.900 |
| SC3 | -18 | 7 | 15.844 |
| SC4 | -25 | 6 | 12.864 |
| SC5 | -34 | 6 | 12.593 |
| A | 2857 mm |
|---|---|
| B | 573 mm |
| C | 525 mm |
| F | 395 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 2535 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2857 mm |
|---|---|
| Width | 573 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.