EA-440AE7-C01 C
23.08 kW
Defrost: None
Product code: EA-535AE4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 9,854 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 114.1 m² |
| Inner volume | 24.2 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 130 kg |
| Quantity | 5 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 825 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 77.0 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-535AE4-C01 C | None |
|---|---|
| EA-535AE4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.92 | 9.97 | 10.04 | 10.10 | 10.09 | 10.01 | 9.88 | 10.12 | 10.78 | 11.69 | 11.43 | 11.35 | 11.24 | 11.10 |
| 5 | 12.60 | 12.78 | 13.01 | 13.20 | 13.25 | 13.19 | 13.02 | 13.23 | 14.05 | 15.20 | 14.74 | 14.59 | 14.37 | 14.05 |
| 6 | 15.10 | 15.59 | 16.03 | 16.39 | 16.56 | 16.52 | 16.35 | 16.53 | 17.51 | 18.94 | 18.28 | 18.03 | 17.66 | 17.08 |
| 7 | 17.32 | 18.06 | 18.74 | 19.33 | 19.68 | 19.83 | 19.74 | 19.93 | 21.09 | 22.82 | 22.01 | 21.69 | 21.20 | 20.41 |
| 8 | 19.31 | 20.35 | 21.17 | 21.98 | 22.49 | 22.73 | 22.74 | 23.01 | 24.39 | 26.42 | 25.64 | 25.30 | 24.78 | 23.86 |
| 9 | 21.15 | 22.38 | 23.59 | 24.64 | 25.32 | 25.69 | 25.77 | 26.07 | 27.63 | 29.91 | 29.05 | 28.64 | 28.03 | 26.99 |
| 10 | 22.83 | 24.38 | 25.90 | 27.23 | 28.11 | 28.64 | 28.80 | 29.15 | 30.90 | 33.44 | 32.50 | 32.04 | 31.34 | 30.13 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 32.495 |
| SC2 | 0 | 8 | 23.007 |
| SC3 | -18 | 7 | 19.491 |
| SC4 | -25 | 6 | 16.033 |
| SC5 | -34 | 6 | 15.227 |
| A | 2857 mm |
|---|---|
| B | 573 mm |
| C | 525 mm |
| F | 395 mm |
| E1 | 5175 mm |
| E2 | 500 mm |
| E | 2535 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2857 mm |
|---|---|
| Width | 573 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.