EA-350AG4-C09 C
41.95 kW
Defrost: Electric
Product code: EA-550AC6-C09 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 33,950 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 116.9 m² |
| Inner volume | 35.3 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 212 kg |
| Quantity | 5 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 3,550 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | E |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-550AC6-C09 C | None |
|---|---|
| EA-550AC6-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 16.86 | 17.10 | 17.38 | 17.59 | 17.59 | 17.45 | 17.21 | 17.35 | 18.32 | 19.69 | 19.04 | 18.79 | 18.44 | 17.91 |
| 5 | 21.39 | 22.24 | 23.01 | 23.68 | 24.05 | 24.11 | 23.92 | 24.14 | 25.59 | 27.63 | 26.75 | 26.46 | 26.04 | 25.40 |
| 6 | 25.07 | 26.43 | 27.48 | 28.55 | 29.26 | 29.70 | 29.89 | 30.34 | 32.26 | 35.03 | 34.29 | 34.01 | 33.58 | 32.91 |
| 7 | 28.42 | 30.14 | 31.87 | 33.39 | 34.47 | 35.18 | 35.55 | 36.12 | 38.42 | 41.76 | 40.90 | 40.55 | 40.03 | 39.17 |
| 8 | 31.25 | 33.74 | 36.04 | 38.10 | 39.59 | 40.62 | 41.22 | 41.95 | 44.64 | 48.58 | 47.62 | 47.21 | 46.59 | 45.55 |
| 9 | ≈ 33.95 | 37.06 | 39.98 | 42.61 | 44.59 | 46.00 | 46.87 | 47.79 | 50.89 | 55.45 | 54.42 | 53.96 | 53.27 | 52.06 |
| 10 | ≈ 36.36 | 40.11 | 43.68 | 46.93 | 49.44 | 51.27 | 52.48 | 53.62 | 57.14 | 62.31 | 61.28 | 60.78 | 60.01 | 58.65 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 61.275 |
| SC2 | 0 | 8 | 41.949 |
| SC3 | -18 | 7 | 33.876 |
| SC4 | -25 | 6 | 27.480 |
| SC5 | -34 | 6 | 25.388 |
| A | 4387 mm |
|---|---|
| B | 590 mm |
| C | 715 mm |
| F | 510 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 4035 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 4387 mm |
|---|---|
| Width | 590 mm |
| Height | 715 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.