EA-363GD10-C13 C
56.51 kW
Defrost: Electric
Product code: EA-563EC10-C11 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 84,253 m³/h |
|---|---|
| Air throw | 49 m |
| External surface | 162.8 m² |
| Inner volume | 68.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 463 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 13,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 75.0 dB(A) |
|---|---|
| Sound power | 98.6 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø54 |
| EA-563EC10-C11 C | None |
|---|---|
| EA-563EC10-C11 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 23.18 | 22.59 | 22.13 | 21.78 | 21.35 | 20.90 | 20.46 | 20.28 | 21.35 | 22.91 | 22.11 | 21.81 | 21.41 | 20.81 |
| 5 | 30.83 | 30.51 | 30.26 | 29.98 | 29.56 | 29.03 | 28.44 | 28.26 | 29.77 | 31.91 | 30.72 | 30.28 | 29.65 | 28.71 |
| 6 | 38.22 | 38.46 | 38.64 | 38.74 | 38.50 | 38.02 | 37.37 | 37.14 | 39.18 | 42.05 | 40.49 | 39.92 | 39.12 | 37.89 |
| 7 | 45.22 | 45.98 | 46.79 | 47.42 | 47.56 | 47.32 | 46.81 | 46.63 | 49.24 | 52.92 | 51.00 | 50.29 | 49.25 | 47.64 |
| 8 | 50.98 | 52.55 | 54.01 | 55.31 | 56.08 | 56.45 | 56.53 | 56.49 | 59.73 | 64.35 | 62.20 | 61.37 | 60.14 | 58.17 |
| 9 | 56.42 | 58.73 | 60.82 | 62.65 | 63.80 | 64.44 | 64.69 | 65.09 | 69.03 | 74.77 | 72.93 | 72.20 | 71.11 | 69.22 |
| 10 | 61.49 | 64.62 | 67.43 | 69.87 | 71.47 | 72.43 | 72.90 | 73.44 | 77.92 | 84.46 | 82.46 | 81.64 | 80.42 | 78.40 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 20.77 | 20.20 | 19.79 | 19.50 | 19.16 | 18.80 | 18.45 | 18.42 | 19.42 | 20.87 | 20.21 | 19.96 | 19.62 | 19.11 |
| 5 | 27.55 | 27.13 | 26.78 | 26.56 | 26.19 | 25.74 | 25.23 | 25.23 | 26.65 | 28.62 | 27.64 | 27.27 | 26.75 | 25.97 |
| 6 | 34.23 | 34.17 | 34.15 | 34.13 | 33.85 | 33.36 | 32.78 | 32.75 | 34.59 | 37.16 | 35.85 | 35.38 | 34.71 | 33.70 |
| 7 | 40.65 | 41.13 | 41.54 | 41.87 | 41.81 | 41.38 | 40.82 | 40.78 | 43.07 | 46.31 | 44.65 | 44.04 | 43.16 | 41.80 |
| 8 | 46.67 | 47.58 | 48.63 | 49.43 | 49.73 | 49.61 | 49.15 | 49.15 | 51.94 | 55.94 | 53.97 | 53.21 | 52.10 | 50.35 |
| 9 | 51.66 | 53.31 | 54.84 | 56.21 | 57.03 | 57.43 | 57.47 | 57.72 | 61.06 | 65.87 | 63.69 | 62.81 | 61.53 | 59.45 |
| 10 | 56.48 | 58.79 | 60.89 | 62.75 | 63.91 | 64.54 | 64.73 | 65.18 | 69.12 | 74.89 | 72.94 | 72.15 | 70.97 | 68.78 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 82.457 | 72.944 |
| SC2 | 0 | 8 | 56.491 | 49.145 |
| SC3 | -18 | 7 | 47.525 | 41.888 |
| SC4 | -25 | 6 | 38.636 | 34.152 |
| SC5 | -34 | 6 | 38.332 | 34.266 |
| A | 4415 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 4035 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø54 |
| Length | 4415 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.