EA-463FD10-C19 C
53.56 kW
Defrost: None
Product code: EA-563FC10-C19 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 61,524 m³/h |
|---|---|
| Air throw | 35 m |
| External surface | 203.5 m² |
| Inner volume | 84.5 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 434 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 6,250 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 91.2 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-563FC10-C19 C | None |
|---|---|
| EA-563FC10-C19 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 22.60 | 22.26 | 22.03 | 21.88 | 21.64 | 21.35 | 21.04 | 20.92 | 22.07 | 23.74 | 22.99 | 22.72 | 22.33 | 21.74 |
| 5 | 29.38 | 29.33 | 29.33 | 29.31 | 29.15 | 28.87 | 28.52 | 28.35 | 29.93 | 32.21 | 31.17 | 30.79 | 30.24 | 29.41 |
| 6 | 35.85 | 36.31 | 36.72 | 37.08 | 37.12 | 36.95 | 36.60 | 36.43 | 38.49 | 41.44 | 40.11 | 39.61 | 38.88 | 37.76 |
| 7 | 41.97 | 43.07 | 43.86 | 44.68 | 45.08 | 45.15 | 44.98 | 44.89 | 47.47 | 51.19 | 49.61 | 49.00 | 48.12 | 46.71 |
| 8 | 47.36 | 49.07 | 50.65 | 52.10 | 53.04 | 53.48 | 53.54 | 53.59 | 56.73 | 61.29 | 59.56 | 58.87 | 57.85 | 56.20 |
| 9 | 52.20 | 54.60 | 56.78 | 58.74 | 60.05 | 60.91 | 61.40 | 61.85 | 65.65 | 71.22 | 69.68 | 68.96 | 67.84 | 65.98 |
| 10 | 56.69 | 59.85 | 62.71 | 65.23 | 66.99 | 68.16 | 68.89 | 69.49 | 73.80 | 80.11 | 78.47 | 77.78 | 76.75 | 75.01 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 20.41 | 20.04 | 19.81 | 19.68 | 19.47 | 19.23 | 18.98 | 19.04 | 20.12 | 21.68 | 21.06 | 20.83 | 20.50 | 20.01 |
| 5 | 26.51 | 26.25 | 26.19 | 26.18 | 26.01 | 25.75 | 25.45 | 25.43 | 26.90 | 29.00 | 28.12 | 27.81 | 27.37 | 26.71 |
| 6 | 32.42 | 32.59 | 32.79 | 33.00 | 32.93 | 32.73 | 32.42 | 32.36 | 34.22 | 36.87 | 35.71 | 35.28 | 34.66 | 33.72 |
| 7 | 38.09 | 38.74 | 39.35 | 39.90 | 40.08 | 40.00 | 39.75 | 39.62 | 41.91 | 45.20 | 43.80 | 43.27 | 42.49 | 41.26 |
| 8 | 43.42 | 44.68 | 45.62 | 46.59 | 47.10 | 47.26 | 47.16 | 47.18 | 49.92 | 53.91 | 52.31 | 51.67 | 50.75 | 49.26 |
| 9 | 48.09 | 49.87 | 51.53 | 53.04 | 54.02 | 54.60 | 54.70 | 54.84 | 58.08 | 62.80 | 61.07 | 60.36 | 59.31 | 57.60 |
| 10 | 52.39 | 54.80 | 57.00 | 58.97 | 60.29 | 61.12 | 61.61 | 62.08 | 65.90 | 71.48 | 69.92 | 69.17 | 68.02 | 66.11 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 78.467 | 69.923 |
| SC2 | 0 | 8 | 53.588 | 47.175 |
| SC3 | -18 | 7 | 44.889 | 40.005 |
| SC4 | -25 | 6 | 36.717 | 32.794 |
| SC5 | -34 | 6 | 36.002 | 32.502 |
| A | 5415 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 5415 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.