EA-463FE10-C13 C
75.53 kW
Defrost: None
Product code: EA-563FD10-C13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 89,227 m³/h |
|---|---|
| Air throw | 52 m |
| External surface | 254.3 m² |
| Inner volume | 104.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 596 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 13,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 71.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-563FD10-C13 C | None |
|---|---|
| EA-563FD10-C13 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 31.00 | 30.62 | 30.33 | 30.08 | 29.67 | 29.17 | 28.64 | 28.45 | 29.97 | 32.17 | 31.06 | 30.65 | 30.08 | 29.21 |
| 5 | 40.46 | 40.65 | 40.79 | 40.86 | 40.54 | 40.07 | 39.45 | 39.25 | 41.43 | 44.50 | 42.96 | 42.38 | 41.54 | 40.25 |
| 6 | 49.35 | 50.42 | 51.30 | 51.97 | 51.93 | 51.69 | 51.17 | 50.99 | 53.84 | 57.91 | 55.93 | 55.19 | 54.13 | 52.49 |
| 7 | 57.62 | 59.35 | 61.16 | 62.72 | 63.46 | 63.64 | 63.38 | 63.35 | 66.99 | 72.20 | 69.87 | 68.96 | 67.64 | 65.52 |
| 8 | 64.24 | 67.16 | 69.80 | 72.13 | 73.63 | 74.52 | 74.94 | 75.48 | 80.09 | 86.80 | 84.40 | 83.39 | 81.88 | 79.43 |
| 9 | 70.59 | 74.58 | 78.16 | 81.28 | 83.40 | 84.72 | 85.45 | 86.19 | 91.50 | 99.25 | 97.02 | 96.12 | 94.75 | 92.50 |
| 10 | 76.43 | 81.55 | 86.16 | 90.20 | 93.02 | 94.87 | 95.96 | 96.95 | 102.99 | 111.82 | 109.42 | 108.42 | 106.92 | 104.39 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 27.47 | 27.00 | 26.68 | 26.46 | 26.12 | 25.73 | 25.32 | 25.31 | 26.70 | 28.71 | 27.81 | 27.48 | 27.01 | 26.30 |
| 5 | 35.85 | 35.72 | 35.58 | 35.56 | 35.30 | 34.88 | 34.36 | 34.31 | 36.26 | 39.01 | 37.75 | 37.30 | 36.64 | 35.63 |
| 6 | 43.89 | 44.36 | 44.78 | 45.14 | 45.09 | 44.76 | 44.20 | 44.12 | 46.63 | 50.18 | 48.50 | 47.89 | 47.00 | 45.66 |
| 7 | 51.50 | 52.76 | 53.86 | 54.56 | 54.92 | 54.85 | 54.46 | 54.42 | 57.54 | 61.98 | 59.96 | 59.18 | 58.06 | 56.28 |
| 8 | 58.23 | 60.33 | 62.21 | 63.90 | 64.84 | 65.14 | 64.98 | 65.06 | 68.85 | 74.32 | 72.02 | 71.11 | 69.77 | 67.55 |
| 9 | 64.33 | 67.19 | 69.80 | 72.11 | 73.61 | 74.51 | 74.92 | 75.48 | 80.09 | 86.84 | 84.39 | 83.37 | 81.81 | 79.24 |
| 10 | 69.92 | 73.72 | 77.14 | 80.14 | 82.18 | 83.44 | 84.12 | 84.84 | 90.06 | 97.68 | 95.45 | 94.48 | 93.02 | 90.59 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 109.422 | 95.448 |
| SC2 | 0 | 8 | 75.479 | 65.064 |
| SC3 | -18 | 7 | 63.094 | 54.762 |
| SC4 | -25 | 6 | 51.300 | 44.784 |
| SC5 | -34 | 6 | 49.660 | 44.053 |
| A | 5415 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| G | 1060 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 5415 mm |
|---|---|
| Width | 1060 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.