EA-291AG7-C04 C
104.65 kW
Defrost: Electric
Product code: EA-563FD4-C08 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 73,309 m³/h |
|---|---|
| Air throw | 43 m |
| External surface | 522.1 m² |
| Inner volume | 107.2 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 635 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 9,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 75.0 dB(A) |
|---|---|
| Sound power | 99.0 dB(A) |
| Energy class | E |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø66,7 |
| EA-563FD4-C08 C | None |
|---|---|
| EA-563FD4-C08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 43.67 | 44.63 | 45.39 | 45.98 | 46.10 | 45.90 | 45.44 | 46.02 | 48.80 | 52.67 | 51.22 | 50.70 | 49.96 | 48.83 |
| 5 | 54.63 | 56.58 | 58.54 | 60.11 | 60.89 | 61.05 | 60.75 | 61.43 | 65.18 | 70.46 | 68.57 | 67.88 | 66.89 | 65.39 |
| 6 | 63.48 | 66.93 | 70.02 | 72.68 | 74.40 | 75.38 | 75.79 | 76.88 | 81.72 | 88.71 | 86.81 | 86.08 | 84.79 | 82.67 |
| 7 | 71.58 | 76.43 | 80.81 | 84.59 | 87.16 | 88.71 | 89.47 | 90.75 | 96.47 | 104.77 | 102.47 | 101.56 | 100.19 | 97.96 |
| 8 | ≈ 78.91 | 85.28 | 91.09 | 96.15 | 99.71 | 102.01 | 103.23 | 104.80 | 111.42 | 121.09 | 118.46 | 117.38 | 115.74 | 113.00 |
| 9 | ≈ 85.49 | 93.44 | 100.78 | 107.27 | 111.99 | 115.16 | 117.00 | 118.92 | 126.50 | 137.61 | 134.70 | 133.46 | 131.57 | 128.34 |
| 10 | ≈ 91.43 | 100.89 | 109.88 | 117.91 | 123.92 | 128.08 | 130.64 | 133.06 | 141.62 | 154.14 | 151.11 | 149.74 | 147.61 | 143.93 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 38.80 | 39.24 | 39.64 | 40.00 | 39.97 | 39.80 | 39.47 | 40.08 | 42.60 | 46.12 | 45.08 | 44.66 | 44.07 | 43.17 |
| 5 | 48.74 | 50.16 | 51.36 | 52.09 | 52.51 | 52.48 | 52.14 | 52.72 | 55.94 | 60.50 | 58.90 | 58.34 | 57.55 | 56.39 |
| 6 | 57.63 | 60.07 | 62.28 | 64.23 | 65.43 | 65.79 | 65.61 | 66.21 | 70.21 | 75.96 | 73.82 | 73.01 | 71.83 | 69.98 |
| 7 | 65.30 | 68.86 | 72.06 | 74.84 | 76.65 | 77.69 | 78.11 | 79.07 | 84.00 | 91.18 | 89.06 | 88.23 | 86.98 | 84.67 |
| 8 | 72.33 | 77.12 | 81.46 | 85.21 | 87.76 | 89.30 | 90.04 | 91.16 | 96.84 | 105.16 | 102.69 | 101.69 | 100.17 | 97.65 |
| 9 | ≈ 78.72 | 84.85 | 90.43 | 95.30 | 98.70 | 100.87 | 102.00 | 103.36 | 109.81 | 119.27 | 116.55 | 115.38 | 113.61 | 110.61 |
| 10 | ≈ 84.49 | 92.00 | 98.92 | 105.01 | 109.34 | 112.24 | 113.87 | 115.60 | 122.87 | 133.48 | 130.57 | 129.25 | 127.24 | 123.79 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 151.112 | 130.570 |
| SC2 | 0 | 8 | 104.798 | 91.164 |
| SC3 | -18 | 7 | 85.749 | 75.667 |
| SC4 | -25 | 6 | 70.020 | 62.283 |
| SC5 | -34 | 6 | 64.293 | 58.232 |
| A | 5415 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| G | 985 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 1 x Ø54 |
| D OUT | 1 x Ø66,7 |
| Length | 5415 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.