EA-463GD7-C13 C
81.65 kW
Defrost: Electric
Product code: EA-563FD7-C08 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 76,886 m³/h |
|---|---|
| Air throw | 45 m |
| External surface | 352.1 m² |
| Inner volume | 106.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 594 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 9,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 75.0 dB(A) |
|---|---|
| Sound power | 99.0 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-563FD7-C08 C | None |
|---|---|
| EA-563FD7-C08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 34.02 | 33.77 | 33.74 | 33.72 | 33.49 | 33.14 | 32.73 | 32.87 | 34.72 | 37.40 | 36.31 | 35.91 | 35.33 | 34.47 |
| 5 | 43.64 | 44.25 | 44.75 | 45.14 | 45.12 | 44.81 | 44.29 | 44.43 | 47.04 | 50.71 | 49.21 | 48.67 | 47.91 | 46.66 |
| 6 | 52.75 | 54.39 | 55.47 | 56.59 | 57.07 | 57.07 | 56.72 | 56.88 | 60.23 | 64.96 | 62.98 | 62.25 | 61.20 | 59.60 |
| 7 | 60.53 | 63.08 | 65.38 | 67.42 | 68.71 | 69.45 | 69.65 | 69.97 | 74.12 | 80.08 | 77.76 | 76.86 | 75.54 | 73.43 |
| 8 | 67.52 | 71.13 | 74.38 | 77.21 | 79.10 | 80.25 | 80.84 | 81.65 | 86.70 | 94.07 | 91.98 | 91.14 | 89.89 | 87.84 |
| 9 | 73.95 | 78.71 | 83.02 | 86.78 | 89.38 | 91.03 | 91.96 | 92.99 | 98.79 | 107.26 | 104.94 | 103.99 | 102.56 | 100.18 |
| 10 | 79.80 | 85.82 | 91.29 | 96.08 | 99.47 | 101.74 | 103.09 | 104.39 | 110.96 | 120.57 | 118.07 | 117.02 | 115.42 | 112.66 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 30.28 | 30.04 | 29.92 | 29.88 | 29.69 | 29.40 | 29.07 | 29.38 | 31.07 | 33.53 | 32.64 | 32.31 | 31.84 | 31.14 |
| 5 | 39.03 | 39.25 | 39.47 | 39.67 | 39.53 | 39.24 | 38.81 | 39.06 | 41.39 | 44.68 | 43.44 | 43.00 | 42.38 | 41.45 |
| 6 | 47.37 | 48.31 | 49.13 | 49.81 | 50.00 | 49.83 | 49.38 | 49.51 | 52.43 | 56.59 | 54.90 | 54.28 | 53.40 | 52.05 |
| 7 | 55.20 | 56.78 | 58.39 | 59.75 | 60.42 | 60.56 | 60.28 | 60.55 | 64.12 | 69.25 | 67.15 | 66.34 | 65.15 | 63.29 |
| 8 | 61.78 | 64.42 | 66.82 | 68.95 | 70.31 | 71.08 | 71.38 | 71.91 | 76.19 | 82.40 | 79.99 | 79.04 | 77.62 | 75.33 |
| 9 | 67.93 | 71.52 | 74.77 | 77.60 | 79.49 | 80.62 | 81.14 | 81.95 | 87.00 | 94.41 | 92.18 | 91.27 | 89.91 | 87.65 |
| 10 | 73.59 | 78.21 | 82.40 | 86.05 | 88.56 | 90.12 | 90.94 | 91.92 | 97.61 | 105.94 | 103.53 | 102.50 | 100.96 | 98.35 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 118.071 | 103.527 |
| SC2 | 0 | 8 | 81.645 | 71.912 |
| SC3 | -18 | 7 | 68.009 | 60.085 |
| SC4 | -25 | 6 | 55.473 | 49.133 |
| SC5 | -34 | 6 | 53.181 | 47.639 |
| A | 5415 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| G | 985 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 5415 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.