EA-291AG7-C04 C
104.65 kW
Defrost: Electric
Product code: EA-563FE4-C19 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 55,394 m³/h |
|---|---|
| Air throw | 33 m |
| External surface | 626.5 m² |
| Inner volume | 127.0 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 582 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 6,250 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø66,7 |
| EA-563FE4-C19 C | None |
|---|---|
| EA-563FE4-C19 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 44.87 | 45.27 | 45.67 | 45.98 | 46.06 | 45.92 | 45.62 | 46.04 | 48.87 | 52.89 | 51.66 | 51.23 | 50.62 | 49.61 |
| 5 | 56.27 | 57.69 | 58.92 | 59.95 | 60.37 | 60.20 | 59.91 | 60.26 | 63.89 | 69.10 | 67.29 | 66.63 | 65.70 | 64.28 |
| 6 | 66.92 | 69.25 | 71.62 | 73.61 | 74.72 | 75.15 | 75.04 | 75.47 | 79.98 | 86.51 | 84.13 | 83.22 | 81.89 | 79.77 |
| 7 | 75.68 | 79.50 | 82.96 | 85.99 | 87.99 | 89.19 | 89.75 | 90.65 | 96.26 | 104.46 | 101.89 | 100.77 | 99.08 | 96.34 |
| 8 | 83.88 | 89.09 | 93.79 | 97.88 | 100.68 | 102.42 | 103.35 | 104.43 | 110.91 | 120.40 | 117.69 | 116.56 | 114.87 | 112.03 |
| 9 | 91.38 | 98.05 | 104.13 | 109.45 | 113.18 | 115.56 | 116.93 | 118.33 | 125.70 | 136.49 | 133.50 | 132.21 | 130.24 | 126.93 |
| 10 | ≈ 98.17 | 106.39 | 113.97 | 120.63 | 125.37 | 128.59 | 130.49 | 132.27 | 140.57 | 152.69 | 149.48 | 148.04 | 145.83 | 142.07 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 39.47 | 39.39 | 39.61 | 39.89 | 39.93 | 39.80 | 39.55 | 40.05 | 42.54 | 46.10 | 45.09 | 44.74 | 44.25 | 43.53 |
| 5 | 49.56 | 50.28 | 50.97 | 51.61 | 51.83 | 51.69 | 51.38 | 51.80 | 54.95 | 59.47 | 57.94 | 57.38 | 56.59 | 55.40 |
| 6 | 59.21 | 60.85 | 62.32 | 63.32 | 63.95 | 64.08 | 63.82 | 64.20 | 68.04 | 73.58 | 71.53 | 70.75 | 69.60 | 67.80 |
| 7 | 68.22 | 70.60 | 73.02 | 75.12 | 76.31 | 76.80 | 76.71 | 77.13 | 81.72 | 88.44 | 85.90 | 84.90 | 83.40 | 80.79 |
| 8 | 75.68 | 79.36 | 82.72 | 85.68 | 87.61 | 88.75 | 89.19 | 90.03 | 95.54 | 103.62 | 100.77 | 99.54 | 97.57 | 94.26 |
| 9 | 82.80 | 87.69 | 92.11 | 95.96 | 98.54 | 100.10 | 100.85 | 101.86 | 108.11 | 117.24 | 114.47 | 113.15 | 111.13 | 107.61 |
| 10 | 89.34 | 95.49 | 101.08 | 105.97 | 109.31 | 111.42 | 112.53 | 113.77 | 120.77 | 130.98 | 127.91 | 126.40 | 124.07 | 119.94 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 149.481 | 127.909 |
| SC2 | 0 | 8 | 104.432 | 90.026 |
| SC3 | -18 | 7 | 86.901 | 75.687 |
| SC4 | -25 | 6 | 71.618 | 62.317 |
| SC5 | -34 | 6 | 67.608 | 59.646 |
| A | 5415 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 1 x Ø54 |
| D OUT | 1 x Ø66,7 |
| Length | 5415 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.