EA-563FG10-C19 C
95.13 kW
Defrost: Electric
Product code: EA-563FE7-C08 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 74,195 m³/h |
|---|---|
| Air throw | 44 m |
| External surface | 422.5 m² |
| Inner volume | 127.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 625 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 9,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 75.0 dB(A) |
|---|---|
| Sound power | 99.0 dB(A) |
| Energy class | E |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø66,7 |
| EA-563FE7-C08 C | None |
|---|---|
| EA-563FE7-C08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 39.89 | 39.60 | 39.56 | 39.56 | 39.30 | 38.90 | 38.40 | 38.71 | 40.89 | 44.07 | 42.83 | 42.36 | 41.71 | 40.73 |
| 5 | 51.07 | 51.72 | 52.27 | 52.71 | 52.66 | 52.24 | 51.63 | 51.91 | 54.97 | 59.28 | 57.56 | 56.93 | 56.05 | 54.73 |
| 6 | 61.69 | 63.48 | 64.68 | 65.90 | 66.40 | 66.32 | 65.81 | 66.16 | 70.05 | 75.57 | 73.26 | 72.41 | 71.19 | 69.31 |
| 7 | 70.99 | 73.84 | 76.44 | 78.73 | 80.15 | 80.80 | 80.57 | 81.03 | 85.84 | 92.74 | 89.96 | 88.88 | 87.29 | 84.76 |
| 8 | 79.22 | 83.28 | 86.94 | 90.14 | 92.22 | 93.43 | 93.93 | 94.92 | 100.78 | 109.32 | 106.73 | 105.69 | 104.14 | 101.06 |
| 9 | 86.79 | 92.19 | 97.06 | 101.28 | 104.16 | 105.91 | 106.78 | 107.98 | 114.67 | 124.47 | 121.55 | 120.34 | 118.54 | 115.52 |
| 10 | 93.71 | 100.55 | 106.74 | 112.14 | 115.91 | 118.33 | 119.64 | 121.11 | 128.65 | 139.71 | 136.55 | 135.20 | 133.16 | 129.70 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 35.12 | 34.82 | 34.68 | 34.65 | 34.44 | 34.12 | 33.73 | 34.17 | 36.26 | 39.15 | 38.15 | 37.77 | 37.25 | 36.45 |
| 5 | 45.17 | 45.33 | 45.54 | 45.69 | 45.60 | 45.26 | 44.75 | 45.11 | 47.82 | 51.66 | 50.23 | 49.73 | 49.03 | 47.99 |
| 6 | 54.76 | 55.70 | 56.55 | 57.26 | 57.44 | 57.20 | 56.62 | 56.92 | 60.28 | 65.07 | 63.05 | 62.34 | 61.31 | 59.74 |
| 7 | 63.81 | 65.76 | 67.16 | 68.58 | 69.26 | 69.34 | 68.94 | 69.25 | 73.31 | 79.18 | 76.70 | 75.76 | 74.38 | 72.19 |
| 8 | 71.71 | 74.56 | 77.17 | 79.50 | 80.95 | 81.72 | 81.57 | 81.98 | 86.83 | 93.88 | 91.02 | 89.89 | 88.21 | 85.48 |
| 9 | 78.89 | 82.80 | 86.35 | 89.46 | 91.48 | 92.65 | 93.12 | 93.98 | 99.73 | 108.16 | 105.50 | 104.39 | 102.44 | 99.20 |
| 10 | 85.53 | 90.61 | 95.20 | 99.20 | 101.84 | 103.47 | 104.25 | 105.32 | 111.79 | 121.24 | 118.35 | 117.10 | 115.21 | 112.03 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 136.552 | 118.348 |
| SC2 | 0 | 8 | 94.915 | 81.984 |
| SC3 | -18 | 7 | 79.390 | 68.932 |
| SC4 | -25 | 6 | 64.680 | 56.545 |
| SC5 | -34 | 6 | 62.173 | 55.036 |
| A | 5415 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| G | 1035 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 1 x Ø54 |
| D OUT | 1 x Ø66,7 |
| Length | 5415 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.