EA-563FE7-C08 C
94.92 kW
Defrost: None
Product code: EA-563FG10-C19 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 56,484 m³/h |
|---|---|
| Air throw | 33 m |
| External surface | 406.9 m² |
| Inner volume | 166.7 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 631 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 6,250 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø80 |
| EA-563FG10-C19 C | None |
|---|---|
| EA-563FG10-C19 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 41.95 | 41.34 | 40.99 | 40.81 | 40.45 | 39.99 | 39.47 | 39.61 | 41.94 | 45.25 | 43.99 | 43.53 | 42.84 | 41.79 |
| 5 | 53.99 | 53.63 | 53.66 | 53.77 | 53.54 | 53.07 | 52.44 | 52.47 | 55.51 | 59.84 | 58.01 | 57.35 | 56.42 | 55.01 |
| 6 | 65.54 | 66.08 | 66.67 | 67.24 | 67.27 | 66.87 | 66.24 | 66.20 | 70.01 | 75.48 | 73.08 | 72.18 | 70.87 | 68.85 |
| 7 | 76.55 | 78.08 | 79.49 | 80.73 | 81.22 | 81.14 | 80.61 | 80.45 | 85.09 | 91.82 | 88.91 | 87.78 | 86.12 | 83.46 |
| 8 | 86.89 | 89.60 | 91.65 | 93.75 | 94.89 | 95.26 | 95.03 | 95.13 | 100.66 | 108.70 | 105.39 | 104.04 | 102.07 | 98.84 |
| 9 | 95.92 | 99.69 | 103.16 | 106.30 | 108.29 | 109.48 | 109.60 | 109.96 | 116.44 | 125.84 | 122.24 | 120.73 | 118.47 | 114.69 |
| 10 | 104.31 | 109.32 | 113.91 | 117.98 | 120.62 | 122.28 | 123.09 | 124.06 | 131.61 | 142.64 | 139.26 | 137.60 | 135.10 | 130.81 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 36.63 | 35.97 | 35.61 | 35.45 | 35.18 | 34.83 | 34.42 | 34.65 | 36.74 | 39.70 | 38.68 | 38.32 | 37.82 | 37.03 |
| 5 | 46.89 | 46.48 | 46.34 | 46.35 | 46.12 | 45.73 | 45.20 | 45.33 | 47.99 | 51.80 | 50.28 | 49.74 | 48.97 | 47.82 |
| 6 | 57.21 | 57.21 | 57.30 | 57.63 | 57.57 | 57.22 | 56.65 | 56.69 | 59.96 | 64.70 | 62.68 | 61.93 | 60.83 | 59.13 |
| 7 | 67.03 | 67.69 | 68.42 | 69.16 | 69.35 | 69.09 | 68.55 | 68.54 | 72.49 | 78.23 | 75.72 | 74.74 | 73.31 | 71.02 |
| 8 | 76.42 | 77.89 | 79.31 | 80.62 | 81.20 | 81.22 | 80.75 | 80.66 | 85.31 | 92.09 | 89.19 | 88.01 | 86.27 | 83.41 |
| 9 | 85.26 | 87.72 | 89.68 | 91.68 | 92.74 | 93.12 | 92.89 | 93.06 | 98.45 | 106.29 | 103.07 | 101.69 | 99.67 | 96.30 |
| 10 | 93.51 | 96.61 | 99.78 | 102.62 | 104.36 | 105.15 | 105.18 | 105.55 | 111.72 | 120.67 | 117.17 | 115.65 | 113.36 | 109.37 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 139.263 | 117.166 |
| SC2 | 0 | 8 | 95.127 | 80.656 |
| SC3 | -18 | 7 | 81.002 | 69.290 |
| SC4 | -25 | 6 | 66.668 | 57.300 |
| SC5 | -34 | 6 | 65.748 | 57.285 |
| A | 5415 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 1 x Ø54 |
| D OUT | 1 x Ø80 |
| Length | 5415 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.