EA-391AE7-C04 C
128.55 kW
Defrost: None
Product code: EA-563FG7-C13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 79,994 m³/h |
|---|---|
| Air throw | 47 m |
| External surface | 563.3 m² |
| Inner volume | 164.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 731 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 13,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 70.0 dB(A) |
|---|---|
| Sound power | 94.2 dB(A) |
| Energy class | E |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø66,7 |
| EA-563FG7-C13 C | None |
|---|---|
| EA-563FG7-C13 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 54.12 | 53.85 | 53.91 | 53.98 | 53.69 | 53.17 | 52.49 | 52.99 | 56.14 | 60.52 | 58.82 | 58.19 | 57.28 | 55.92 |
| 5 | 68.92 | 69.96 | 70.84 | 71.55 | 71.57 | 71.05 | 70.25 | 70.71 | 74.88 | 80.80 | 78.43 | 77.59 | 76.38 | 74.56 |
| 6 | 82.90 | 85.48 | 87.24 | 89.02 | 89.79 | 89.76 | 89.11 | 89.60 | 94.88 | 102.41 | 99.22 | 98.05 | 96.35 | 93.73 |
| 7 | 95.07 | 99.06 | 102.68 | 105.86 | 107.84 | 108.90 | 108.63 | 109.27 | 115.75 | 125.09 | 121.29 | 119.80 | 117.59 | 114.07 |
| 8 | 105.93 | 111.55 | 116.62 | 121.02 | 123.90 | 125.55 | 126.21 | 127.50 | 135.34 | 146.81 | 143.21 | 141.75 | 139.57 | 135.42 |
| 9 | 115.91 | 123.31 | 130.01 | 135.81 | 139.77 | 142.16 | 143.31 | 144.87 | 153.80 | 166.90 | 162.89 | 161.21 | 158.68 | 154.41 |
| 10 | 125.02 | 134.33 | 142.81 | 150.19 | 155.28 | 158.58 | 160.32 | 162.31 | 172.39 | 187.11 | 182.80 | 180.92 | 178.05 | 173.16 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 45.97 | 45.61 | 45.48 | 45.48 | 45.23 | 44.84 | 44.38 | 45.03 | 47.86 | 51.79 | 50.60 | 50.15 | 49.47 | 48.45 |
| 5 | 58.81 | 59.03 | 59.33 | 59.56 | 59.46 | 59.06 | 58.48 | 58.93 | 62.50 | 67.55 | 65.65 | 65.00 | 64.09 | 62.75 |
| 6 | 71.07 | 72.24 | 73.31 | 74.24 | 74.45 | 74.19 | 73.54 | 73.78 | 78.15 | 84.39 | 81.80 | 80.85 | 79.48 | 77.34 |
| 7 | 82.66 | 85.06 | 86.82 | 88.59 | 89.41 | 89.51 | 89.09 | 89.34 | 94.57 | 102.15 | 99.00 | 97.78 | 95.98 | 93.09 |
| 8 | 93.41 | 96.60 | 99.88 | 102.80 | 104.52 | 105.11 | 104.99 | 105.37 | 111.57 | 120.62 | 116.99 | 115.53 | 113.33 | 109.74 |
| 9 | 102.31 | 107.22 | 111.68 | 115.58 | 118.06 | 119.44 | 120.08 | 121.09 | 128.46 | 139.25 | 135.38 | 133.69 | 131.14 | 126.93 |
| 10 | 110.93 | 117.31 | 123.08 | 128.08 | 131.30 | 133.29 | 134.30 | 135.56 | 143.84 | 155.93 | 152.20 | 150.56 | 148.08 | 143.84 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 182.801 | 152.204 |
| SC2 | 0 | 8 | 127.499 | 105.372 |
| SC3 | -18 | 7 | 106.781 | 89.025 |
| SC4 | -25 | 6 | 87.237 | 73.312 |
| SC5 | -34 | 6 | 83.587 | 71.419 |
| A | 5415 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| G | 1210 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 2 x Ø35 |
| D OUT | 2 x Ø66,7 |
| Length | 5415 mm |
|---|---|
| Width | 1210 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.