EA-163ED10-C01 C
9.63 kW
Defrost: None
Product code: EA-630BC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,787 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 25.6 m² |
| Inner volume | 11.7 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 77 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 372 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 72.0 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-630BC10-C01 C | None |
|---|---|
| EA-630BC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.88 | 3.90 | 3.92 | 3.94 | 3.93 | 3.89 | 3.84 | 3.89 | 4.12 | 4.45 | 4.31 | 4.26 | 4.18 | 4.07 |
| 5 | 4.96 | 5.07 | 5.17 | 5.26 | 5.29 | 5.28 | 5.24 | 5.29 | 5.61 | 6.06 | 5.88 | 5.81 | 5.72 | 5.59 |
| 6 | 6.01 | 6.23 | 6.43 | 6.60 | 6.70 | 6.72 | 6.71 | 6.77 | 7.18 | 7.77 | 7.54 | 7.45 | 7.33 | 7.12 |
| 7 | 6.93 | 7.26 | 7.57 | 7.84 | 8.03 | 8.15 | 8.19 | 8.28 | 8.79 | 9.53 | 9.28 | 9.18 | 9.03 | 8.78 |
| 8 | 7.74 | 8.19 | 8.61 | 8.93 | 9.20 | 9.38 | 9.48 | 9.62 | 10.23 | 11.13 | 10.91 | 10.81 | 10.66 | 10.42 |
| 9 | 8.48 | 9.07 | 9.55 | 10.03 | 10.38 | 10.62 | 10.77 | 10.94 | 11.64 | 12.67 | 12.43 | 12.33 | 12.16 | 11.88 |
| 10 | 9.16 | 9.82 | 10.49 | 11.08 | 11.52 | 11.84 | 12.05 | 12.27 | 13.06 | 14.22 | 13.97 | 13.85 | 13.67 | 13.35 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.970 |
| SC2 | 0 | 8 | 9.622 |
| SC3 | -18 | 7 | 7.927 |
| SC4 | -25 | 6 | 6.426 |
| SC5 | -34 | 6 | 6.062 |
| A | 2557 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 385 mm |
| E2 | 367 mm |
| E | 2235 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2557 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.