EA-145AG7-C01 C
9.48 kW
Defrost: Electric
Product code: EA-630BC8-C05 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,651 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 31.1 m² |
| Inner volume | 11.7 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 59 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 720 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-630BC8-C05 C | None |
|---|---|
| EA-630BC8-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.85 | 3.87 | 3.90 | 3.92 | 3.91 | 3.87 | 3.82 | 3.89 | 4.14 | 4.47 | 4.36 | 4.31 | 4.24 | 4.14 |
| 5 | 4.92 | 5.02 | 5.12 | 5.21 | 5.24 | 5.22 | 5.17 | 5.24 | 5.57 | 6.02 | 5.84 | 5.78 | 5.70 | 5.58 |
| 6 | 5.96 | 6.17 | 6.36 | 6.53 | 6.60 | 6.63 | 6.59 | 6.67 | 7.08 | 7.66 | 7.42 | 7.33 | 7.20 | 6.99 |
| 7 | 6.88 | 7.20 | 7.50 | 7.76 | 7.94 | 8.04 | 8.06 | 8.13 | 8.63 | 9.36 | 9.08 | 8.97 | 8.80 | 8.53 |
| 8 | 7.68 | 8.12 | 8.53 | 8.85 | 9.10 | 9.25 | 9.32 | 9.46 | 10.06 | 10.93 | 10.68 | 10.57 | 10.40 | 10.11 |
| 9 | 8.41 | 8.99 | 9.46 | 9.93 | 10.26 | 10.47 | 10.58 | 10.75 | 11.43 | 12.42 | 12.15 | 12.02 | 11.83 | 11.49 |
| 10 | 9.09 | 9.74 | 10.39 | 10.96 | 11.39 | 11.68 | 11.84 | 12.05 | 12.81 | 13.93 | 13.63 | 13.49 | 13.27 | 12.89 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.632 |
| SC2 | 0 | 8 | 9.464 |
| SC3 | -18 | 7 | 7.845 |
| SC4 | -25 | 6 | 6.362 |
| SC5 | -34 | 6 | 6.009 |
| A | 2557 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 385 mm |
| E2 | 367 mm |
| E | 2235 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2407 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.