EA-163GC10-C08 C
14.53 kW
Defrost: Electric
Product code: EA-630BE6-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,404 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 59.9 m² |
| Inner volume | 16.5 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 90 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 372 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 74.1 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-630BE6-C01 C | None |
|---|---|
| EA-630BE6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.11 | 6.23 | 6.34 | 6.43 | 6.45 | 6.41 | 6.33 | 6.49 | 6.91 | 7.48 | 7.30 | 7.24 | 7.16 | 7.04 |
| 5 | 7.68 | 7.94 | 8.17 | 8.34 | 8.43 | 8.43 | 8.35 | 8.49 | 9.02 | 9.77 | 9.46 | 9.35 | 9.19 | 8.95 |
| 6 | 9.09 | 9.53 | 9.92 | 10.26 | 10.45 | 10.51 | 10.43 | 10.58 | 11.22 | 12.15 | 11.75 | 11.59 | 11.33 | 10.95 |
| 7 | 10.32 | 10.93 | 11.48 | 11.95 | 12.20 | 12.36 | 12.39 | 12.58 | 13.35 | 14.49 | 14.08 | 13.89 | 13.58 | 13.07 |
| 8 | 11.44 | 12.24 | 12.88 | 13.50 | 13.94 | 14.17 | 14.25 | 14.46 | 15.35 | 16.65 | 16.19 | 15.98 | 15.66 | 15.10 |
| 9 | 12.45 | 13.36 | 14.27 | 15.07 | 15.62 | 15.96 | 16.10 | 16.36 | 17.36 | 18.82 | 18.33 | 18.08 | 17.71 | 17.06 |
| 10 | ≈ 13.36 | 14.47 | 15.58 | 16.58 | 17.27 | 17.73 | 17.94 | 18.25 | 19.38 | 21.01 | 20.48 | 20.21 | 19.79 | 19.04 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.478 |
| SC2 | 0 | 8 | 14.464 |
| SC3 | -18 | 7 | 12.031 |
| SC4 | -25 | 6 | 9.923 |
| SC5 | -34 | 6 | 9.197 |
| A | 2557 mm |
|---|---|
| B | 573 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 385 mm |
| E2 | 367 mm |
| E | 2235 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 2557 mm |
|---|---|
| Width | 573 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.