EA-163EC4-C01 C
11.67 kW
Defrost: Electric
Product code: EA-630BE8-C05 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,724 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 46.2 m² |
| Inner volume | 16.3 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 73 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 720 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-630BE8-C05 C | None |
|---|---|
| EA-630BE8-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.92 | 4.93 | 4.95 | 4.98 | 4.96 | 4.91 | 4.84 | 4.96 | 5.28 | 5.72 | 5.58 | 5.53 | 5.48 | 5.40 |
| 5 | 6.25 | 6.35 | 6.44 | 6.53 | 6.55 | 6.51 | 6.44 | 6.53 | 6.93 | 7.50 | 7.26 | 7.17 | 7.06 | 6.89 |
| 6 | 7.56 | 7.76 | 7.93 | 8.10 | 8.18 | 8.17 | 8.11 | 8.18 | 8.67 | 9.38 | 9.07 | 8.95 | 8.77 | 8.48 |
| 7 | 8.75 | 9.09 | 9.41 | 9.68 | 9.83 | 9.86 | 9.82 | 9.90 | 10.49 | 11.35 | 10.98 | 10.83 | 10.60 | 10.23 |
| 8 | 9.83 | 10.30 | 10.75 | 11.14 | 11.39 | 11.51 | 11.51 | 11.63 | 12.31 | 13.33 | 12.93 | 12.75 | 12.48 | 12.02 |
| 9 | 10.79 | 11.42 | 12.00 | 12.45 | 12.78 | 12.97 | 13.05 | 13.22 | 14.02 | 15.20 | 14.82 | 14.64 | 14.37 | 13.86 |
| 10 | 11.68 | 12.48 | 13.13 | 13.75 | 14.19 | 14.46 | 14.58 | 14.78 | 15.69 | 17.01 | 16.60 | 16.40 | 16.09 | 15.55 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.599 |
| SC2 | 0 | 8 | 11.629 |
| SC3 | -18 | 7 | 9.754 |
| SC4 | -25 | 6 | 7.928 |
| SC5 | -34 | 6 | 7.609 |
| A | 2557 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 385 mm |
| E2 | 367 mm |
| E | 2235 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2407 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.