EA-563FG7-C19 C
105.57 kW
Defrost: Electric
Product code: EA-663EG4-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 40,755 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 801.9 m² |
| Inner volume | 160.4 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 700 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 3,600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 83.9 dB(A) |
| Energy class | C |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø80 |
| EA-663EG4-C01 C | None |
|---|---|
| EA-663EG4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 48.26 | 48.29 | 48.53 | 48.87 | 48.90 | 48.68 | 48.24 | 49.26 | 52.45 | 56.93 | 55.67 | 55.26 | 54.69 | 53.89 |
| 5 | 60.46 | 61.05 | 61.75 | 62.44 | 62.56 | 62.34 | 61.76 | 62.57 | 66.42 | 71.98 | 69.95 | 69.21 | 68.15 | 66.52 |
| 6 | 72.00 | 73.50 | 74.92 | 76.19 | 76.70 | 76.58 | 75.88 | 76.52 | 81.07 | 87.74 | 84.90 | 83.83 | 82.20 | 79.54 |
| 7 | 82.89 | 85.54 | 87.57 | 89.62 | 90.67 | 90.85 | 90.25 | 90.82 | 96.13 | 103.93 | 100.47 | 99.02 | 96.84 | 93.23 |
| 8 | 93.03 | 96.41 | 99.88 | 102.94 | 104.76 | 105.28 | 104.87 | 105.48 | 111.62 | 120.56 | 116.56 | 114.78 | 112.08 | 107.55 |
| 9 | 101.55 | 106.61 | 111.21 | 115.22 | 117.74 | 118.92 | 119.07 | 120.03 | 127.16 | 137.44 | 132.92 | 130.82 | 127.64 | 122.24 |
| 10 | 109.81 | 116.28 | 122.16 | 127.24 | 130.45 | 132.21 | 132.64 | 133.74 | 141.68 | 153.15 | 148.63 | 146.48 | 143.17 | 137.20 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 148.633 |
| SC2 | 0 | 8 | 105.479 |
| SC3 | -18 | 7 | 90.152 |
| SC4 | -25 | 6 | 74.923 |
| SC5 | -34 | 6 | 72.409 |
| A | 5215 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 4835 mm |
| D IN | 1 x Ø54 |
| D OUT | 1 x Ø80 |
| Length | 5215 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.