EA-HL-150AC7-A10 C
11.05 kW
Defrost: None
Product code: EA-HL-150AC10-A10 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,128 m³/h |
|---|---|
| Air throw | 21 m |
| External surface | 23.3 m² |
| Inner volume | 10.9 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 83 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 690 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-HL-150AC10-A10 C | None |
|---|---|
| EA-HL-150AC10-A10 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.66 | 3.66 | 3.66 | 3.66 | 3.64 | 3.60 | 3.55 | 3.53 | 3.72 | 4.00 | 3.86 | 3.81 | 3.74 | 3.63 |
| 5 | 4.72 | 4.80 | 4.88 | 4.94 | 4.96 | 4.95 | 4.91 | 4.89 | 5.17 | 5.57 | 5.39 | 5.32 | 5.23 | 5.08 |
| 6 | 5.76 | 5.94 | 6.11 | 6.26 | 6.32 | 6.36 | 6.35 | 6.36 | 6.73 | 7.27 | 7.06 | 6.98 | 6.86 | 6.67 |
| 7 | 6.69 | 6.99 | 7.26 | 7.52 | 7.69 | 7.80 | 7.84 | 7.88 | 8.35 | 9.03 | 8.80 | 8.71 | 8.58 | 8.36 |
| 8 | 7.49 | 7.90 | 8.28 | 8.63 | 8.84 | 9.01 | 9.14 | 9.25 | 9.84 | 10.70 | 10.51 | 10.43 | 10.31 | 10.11 |
| 9 | 8.22 | 8.76 | 9.20 | 9.65 | 9.99 | 10.23 | 10.40 | 10.55 | 11.22 | 12.22 | 12.02 | 11.94 | 11.81 | 11.59 |
| 10 | 8.88 | 9.50 | 10.12 | 10.69 | 11.11 | 11.43 | 11.66 | 11.85 | 12.62 | 13.75 | 13.55 | 13.46 | 13.32 | 13.08 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.30 | 3.28 | 3.27 | 3.27 | 3.25 | 3.21 | 3.17 | 3.17 | 3.35 | 3.60 | 3.49 | 3.45 | 3.39 | 3.30 |
| 5 | 4.26 | 4.31 | 4.35 | 4.39 | 4.40 | 4.38 | 4.34 | 4.34 | 4.59 | 4.95 | 4.80 | 4.74 | 4.66 | 4.54 |
| 6 | 5.22 | 5.31 | 5.43 | 5.54 | 5.59 | 5.60 | 5.59 | 5.60 | 5.92 | 6.40 | 6.21 | 6.14 | 6.03 | 5.87 |
| 7 | 6.09 | 6.31 | 6.51 | 6.69 | 6.81 | 6.85 | 6.87 | 6.90 | 7.32 | 7.92 | 7.70 | 7.62 | 7.50 | 7.30 |
| 8 | 6.89 | 7.20 | 7.50 | 7.77 | 7.96 | 8.10 | 8.18 | 8.22 | 8.72 | 9.46 | 9.24 | 9.14 | 9.01 | 8.78 |
| 9 | 7.59 | 8.01 | 8.40 | 8.76 | 8.98 | 9.16 | 9.29 | 9.41 | 10.01 | 10.89 | 10.70 | 10.61 | 10.49 | 10.27 |
| 10 | 8.23 | 8.77 | 9.22 | 9.66 | 10.00 | 10.24 | 10.41 | 10.57 | 11.24 | 12.24 | 12.04 | 11.95 | 11.82 | 11.58 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 13.549 | 12.040 |
| SC2 | 0 | 8 | 9.248 | 8.222 |
| SC3 | -18 | 7 | 7.595 | 6.746 |
| SC4 | -25 | 6 | 6.110 | 5.430 |
| SC5 | -34 | 6 | 5.806 | 5.250 |
| A | 1387 mm |
|---|---|
| B | 590 mm |
| C | 875 mm |
| F | 510 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1387 mm |
|---|---|
| Width | 590 mm |
| Height | 875 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.