EB-325AA4-B05 C
3.06 kW
Defrost: Electric
Product code: EB-130BE4-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,201 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 14.8 m² |
| Inner volume | 2.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 24 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 62 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 64.9 dB(A) |
| Energy class | B |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EB-130BE4-B01 C | None |
|---|---|
| EB-130BE4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.35 | 1.35 | 1.36 | 1.37 | 1.37 | 1.37 | 1.36 | 1.38 | 1.47 | 1.59 | 1.56 | 1.54 | 1.53 | 1.51 |
| 5 | 1.69 | 1.71 | 1.74 | 1.76 | 1.77 | 1.77 | 1.76 | 1.78 | 1.89 | 2.04 | 1.99 | 1.97 | 1.94 | 1.89 |
| 6 | 2.02 | 2.07 | 2.12 | 2.16 | 2.18 | 2.19 | 2.18 | 2.19 | 2.32 | 2.52 | 2.44 | 2.41 | 2.36 | 2.29 |
| 7 | 2.34 | 2.42 | 2.50 | 2.56 | 2.60 | 2.62 | 2.61 | 2.63 | 2.78 | 3.01 | 2.92 | 2.88 | 2.82 | 2.72 |
| 8 | 2.62 | 2.73 | 2.84 | 2.93 | 2.99 | 3.03 | 3.03 | 3.06 | 3.25 | 3.51 | 3.40 | 3.36 | 3.29 | 3.17 |
| 9 | 2.88 | 3.03 | 3.17 | 3.29 | 3.37 | 3.42 | 3.43 | 3.46 | 3.67 | 3.98 | 3.87 | 3.82 | 3.75 | 3.62 |
| 10 | 3.15 | 3.34 | 3.51 | 3.65 | 3.74 | 3.80 | 3.83 | 3.87 | 4.10 | 4.44 | 4.33 | 4.27 | 4.19 | 4.04 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 4.325 |
| SC2 | 0 | 8 | 3.063 |
| SC3 | -18 | 7 | 2.581 |
| SC4 | -25 | 6 | 2.120 |
| SC5 | -34 | 6 | 2.037 |
| A | 857 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E | 535 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 857 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.