EB-425BC4-B05 C
7.03 kW
Defrost: Electric
Product code: EB-145AE7-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,605 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 18.1 m² |
| Inner volume | 5.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 46 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 490 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-145AE7-B01 C | None |
|---|---|
| EB-145AE7-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.86 | 2.80 | 2.76 | 2.73 | 2.69 | 2.64 | 2.59 | 2.63 | 2.78 | 3.00 | 2.90 | 2.87 | 2.82 | 2.75 |
| 5 | 3.78 | 3.76 | 3.75 | 3.74 | 3.70 | 3.64 | 3.57 | 3.60 | 3.82 | 4.11 | 3.97 | 3.93 | 3.87 | 3.79 |
| 6 | 4.68 | 4.73 | 4.77 | 4.81 | 4.79 | 4.74 | 4.66 | 4.68 | 4.95 | 5.33 | 5.12 | 5.05 | 4.95 | 4.81 |
| 7 | 5.54 | 5.66 | 5.78 | 5.89 | 5.92 | 5.89 | 5.81 | 5.83 | 6.16 | 6.64 | 6.38 | 6.29 | 6.14 | 5.92 |
| 8 | 6.27 | 6.46 | 6.65 | 6.82 | 6.92 | 6.95 | 6.94 | 7.00 | 7.42 | 8.02 | 7.73 | 7.61 | 7.43 | 7.15 |
| 9 | 7.01 | 7.28 | 7.53 | 7.73 | 7.87 | 7.94 | 7.94 | 8.01 | 8.49 | 9.19 | 8.93 | 8.82 | 8.66 | 8.38 |
| 10 | 7.67 | 8.03 | 8.37 | 8.66 | 8.84 | 8.92 | 8.95 | 9.03 | 9.57 | 10.36 | 10.08 | 9.95 | 9.76 | 9.43 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.080 |
| SC2 | 0 | 8 | 7.000 |
| SC3 | -18 | 7 | 5.907 |
| SC4 | -25 | 6 | 4.772 |
| SC5 | -34 | 6 | 4.699 |
| A | 1017 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E | 685 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1017 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.