EB-325AC6-B05 C
4.47 kW
Defrost: Electric
Product code: EB-230AC4-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,478 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 16.5 m² |
| Inner volume | 2.9 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 31 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 67.5 dB(A) |
| Energy class | C |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EB-230AC4-B01 C | None |
|---|---|
| EB-230AC4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.85 | 1.89 | 1.92 | 1.95 | 1.96 | 1.95 | 1.94 | 1.97 | 2.09 | 2.27 | 2.22 | 2.20 | 2.17 | 2.14 |
| 5 | 2.33 | 2.41 | 2.49 | 2.56 | 2.59 | 2.60 | 2.59 | 2.62 | 2.78 | 3.01 | 2.93 | 2.90 | 2.86 | 2.80 |
| 6 | 2.74 | 2.87 | 2.99 | 3.09 | 3.16 | 3.20 | 3.22 | 3.27 | 3.47 | 3.77 | 3.69 | 3.66 | 3.61 | 3.52 |
| 7 | 3.14 | 3.32 | 3.48 | 3.63 | 3.72 | 3.78 | 3.81 | 3.86 | 4.10 | 4.46 | 4.36 | 4.32 | 4.25 | 4.15 |
| 8 | 3.49 | 3.73 | 3.95 | 4.14 | 4.28 | 4.36 | 4.40 | 4.46 | 4.74 | 5.15 | 5.04 | 4.98 | 4.91 | 4.78 |
| 9 | 3.81 | 4.11 | 4.39 | 4.64 | 4.82 | 4.93 | 4.98 | 5.06 | 5.38 | 5.84 | 5.72 | 5.66 | 5.58 | 5.42 |
| 10 | ≈ 4.09 | 4.46 | 4.81 | 5.12 | 5.31 | 5.47 | 5.56 | 5.66 | 6.02 | 6.55 | 6.42 | 6.35 | 6.26 | 6.08 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.417 |
| SC2 | 0 | 8 | 4.461 |
| SC3 | -18 | 7 | 3.661 |
| SC4 | -25 | 6 | 2.988 |
| SC5 | -34 | 6 | 2.769 |
| A | 1197 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E | 875 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 1197 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.