EB-135AE7-B01 C
4.73 kW
Defrost: None
Product code: EB-230AE4-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,858 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 24.7 m² |
| Inner volume | 4.2 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 32 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EB-230AE4-B05 C | None |
|---|---|
| EB-230AE4-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.03 | 2.07 | 2.11 | 2.15 | 2.17 | 2.16 | 2.15 | 2.20 | 2.34 | 2.54 | 2.48 | 2.46 | 2.43 | 2.40 |
| 5 | 2.52 | 2.60 | 2.68 | 2.75 | 2.79 | 2.80 | 2.78 | 2.82 | 3.00 | 3.25 | 3.16 | 3.12 | 3.07 | 2.98 |
| 6 | 2.97 | 3.11 | 3.23 | 3.34 | 3.41 | 3.44 | 3.43 | 3.48 | 3.69 | 4.00 | 3.87 | 3.82 | 3.75 | 3.63 |
| 7 | 3.36 | 3.56 | 3.73 | 3.88 | 3.98 | 4.04 | 4.05 | 4.11 | 4.36 | 4.73 | 4.60 | 4.55 | 4.46 | 4.29 |
| 8 | 3.77 | 4.01 | 4.23 | 4.41 | 4.55 | 4.62 | 4.65 | 4.71 | 5.00 | 5.42 | 5.28 | 5.21 | 5.11 | 4.93 |
| 9 | 4.11 | 4.41 | 4.70 | 4.95 | 5.11 | 5.22 | 5.25 | 5.32 | 5.65 | 6.12 | 5.96 | 5.89 | 5.77 | 5.56 |
| 10 | ≈ 4.41 | 4.79 | 5.14 | 5.45 | 5.66 | 5.79 | 5.86 | 5.94 | 6.30 | 6.81 | 6.64 | 6.56 | 6.42 | 6.19 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.641 |
| SC2 | 0 | 8 | 4.713 |
| SC3 | -18 | 7 | 3.930 |
| SC4 | -25 | 6 | 3.232 |
| SC5 | -34 | 6 | 3.000 |
| A | 1197 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E | 875 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1197 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.