EB-330BB6-B05 C
5.19 kW
Defrost: Electric
Product code: EB-230AE6-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,322 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 17.9 m² |
| Inner volume | 4.2 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 34 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 68.3 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EB-230AE6-B01 C | None |
|---|---|
| EB-230AE6-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.18 | 2.23 | 2.29 | 2.33 | 2.35 | 2.35 | 2.33 | 2.37 | 2.52 | 2.74 | 2.67 | 2.64 | 2.61 | 2.57 |
| 5 | 2.70 | 2.81 | 2.91 | 3.00 | 3.05 | 3.07 | 3.06 | 3.10 | 3.29 | 3.57 | 3.46 | 3.42 | 3.37 | 3.27 |
| 6 | 3.17 | 3.34 | 3.49 | 3.63 | 3.72 | 3.77 | 3.79 | 3.84 | 4.08 | 4.43 | 4.31 | 4.25 | 4.18 | 4.04 |
| 7 | 3.59 | 3.82 | 4.03 | 4.22 | 4.34 | 4.42 | 4.45 | 4.52 | 4.80 | 5.21 | 5.08 | 5.03 | 4.94 | 4.80 |
| 8 | 4.01 | 4.31 | 4.57 | 4.81 | 4.97 | 5.07 | 5.12 | 5.20 | 5.52 | 5.99 | 5.85 | 5.79 | 5.68 | 5.50 |
| 9 | 4.37 | 4.73 | 5.07 | 5.37 | 5.58 | 5.72 | 5.79 | 5.88 | 6.25 | 6.76 | 6.61 | 6.54 | 6.42 | 6.21 |
| 10 | ≈ 4.69 | 5.13 | 5.54 | 5.90 | 6.17 | 6.32 | 6.42 | 6.54 | 6.96 | 7.55 | 7.39 | 7.31 | 7.18 | 6.93 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.389 |
| SC2 | 0 | 8 | 5.197 |
| SC3 | -18 | 7 | 4.275 |
| SC4 | -25 | 6 | 3.493 |
| SC5 | -34 | 6 | 3.213 |
| A | 1197 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E | 875 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1197 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.