EB-330AB7-B05 C
4.19 kW
Defrost: Electric
Product code: EB-230BB4-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,840 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 14.6 m² |
| Inner volume | 2.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 31 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 67.5 dB(A) |
| Energy class | C |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EB-230BB4-B01 C | None |
|---|---|
| EB-230BB4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.75 | 1.74 | 1.75 | 1.75 | 1.74 | 1.72 | 1.70 | 1.71 | 1.82 | 1.96 | 1.91 | 1.89 | 1.86 | 1.82 |
| 5 | 2.26 | 2.29 | 2.33 | 2.35 | 2.36 | 2.35 | 2.32 | 2.34 | 2.47 | 2.67 | 2.59 | 2.56 | 2.52 | 2.47 |
| 6 | 2.71 | 2.78 | 2.85 | 2.92 | 2.96 | 2.98 | 2.99 | 3.02 | 3.19 | 3.45 | 3.35 | 3.31 | 3.25 | 3.17 |
| 7 | 3.13 | 3.25 | 3.35 | 3.44 | 3.51 | 3.54 | 3.56 | 3.59 | 3.81 | 4.13 | 4.04 | 4.00 | 3.95 | 3.86 |
| 8 | 3.52 | 3.68 | 3.84 | 3.97 | 4.06 | 4.11 | 4.13 | 4.17 | 4.43 | 4.81 | 4.70 | 4.66 | 4.59 | 4.48 |
| 9 | 3.88 | 4.10 | 4.30 | 4.48 | 4.60 | 4.68 | 4.72 | 4.76 | 5.05 | 5.49 | 5.37 | 5.32 | 5.24 | 5.11 |
| 10 | 4.21 | 4.49 | 4.75 | 4.98 | 5.12 | 5.23 | 5.29 | 5.36 | 5.69 | 6.18 | 6.05 | 5.99 | 5.90 | 5.75 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.053 |
| SC2 | 0 | 8 | 4.174 |
| SC3 | -18 | 7 | 3.470 |
| SC4 | -25 | 6 | 2.852 |
| SC5 | -34 | 6 | 2.725 |
| A | 1357 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E | 1035 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 1357 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.