EB-225BC7-B05 C
3.02 kW
Defrost: Electric
Product code: EB-230BB7-B05 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,668 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 9.2 m² |
| Inner volume | 2.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 29 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EB-230BB7-B05 C | None |
|---|---|
| EB-230BB7-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.23 | 1.20 | 1.18 | 1.17 | 1.16 | 1.14 | 1.12 | 1.13 | 1.19 | 1.28 | 1.24 | 1.23 | 1.21 | 1.18 |
| 5 | 1.62 | 1.61 | 1.60 | 1.60 | 1.59 | 1.57 | 1.54 | 1.54 | 1.63 | 1.76 | 1.70 | 1.68 | 1.66 | 1.62 |
| 6 | 2.02 | 2.02 | 2.04 | 2.05 | 2.05 | 2.03 | 2.01 | 2.01 | 2.12 | 2.29 | 2.21 | 2.18 | 2.14 | 2.09 |
| 7 | 2.40 | 2.44 | 2.47 | 2.51 | 2.53 | 2.52 | 2.51 | 2.51 | 2.65 | 2.86 | 2.77 | 2.73 | 2.68 | 2.60 |
| 8 | 2.72 | 2.79 | 2.86 | 2.93 | 2.97 | 3.00 | 3.01 | 3.03 | 3.21 | 3.46 | 3.36 | 3.32 | 3.26 | 3.16 |
| 9 | 3.05 | 3.15 | 3.23 | 3.32 | 3.38 | 3.42 | 3.44 | 3.47 | 3.68 | 4.00 | 3.91 | 3.87 | 3.82 | 3.73 |
| 10 | 3.35 | 3.48 | 3.61 | 3.72 | 3.80 | 3.85 | 3.88 | 3.92 | 4.16 | 4.51 | 4.42 | 4.38 | 4.31 | 4.21 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 4.416 |
| SC2 | 0 | 8 | 3.027 |
| SC3 | -18 | 7 | 2.520 |
| SC4 | -25 | 6 | 2.037 |
| SC5 | -34 | 6 | 2.021 |
| A | 1357 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E | 1035 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 1357 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.