EB-330AC6-B01 C
5.97 kW
Defrost: Electric
Product code: EB-230BE4-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,402 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 29.5 m² |
| Inner volume | 5.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 39 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 67.9 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EB-230BE4-B01 C | None |
|---|---|
| EB-230BE4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.55 | 2.60 | 2.66 | 2.71 | 2.73 | 2.73 | 2.72 | 2.77 | 2.94 | 3.19 | 3.12 | 3.09 | 3.06 | 3.01 |
| 5 | 3.15 | 3.27 | 3.37 | 3.47 | 3.52 | 3.54 | 3.53 | 3.57 | 3.79 | 4.11 | 4.00 | 3.96 | 3.89 | 3.79 |
| 6 | 3.71 | 3.88 | 4.05 | 4.20 | 4.29 | 4.35 | 4.36 | 4.41 | 4.68 | 5.08 | 4.93 | 4.87 | 4.78 | 4.64 |
| 7 | 4.19 | 4.44 | 4.67 | 4.87 | 5.01 | 5.09 | 5.12 | 5.19 | 5.51 | 5.98 | 5.83 | 5.77 | 5.67 | 5.50 |
| 8 | 4.69 | 5.01 | 5.30 | 5.55 | 5.71 | 5.82 | 5.88 | 5.96 | 6.33 | 6.86 | 6.70 | 6.62 | 6.50 | 6.29 |
| 9 | 5.11 | 5.51 | 5.87 | 6.20 | 6.42 | 6.57 | 6.64 | 6.73 | 7.15 | 7.75 | 7.57 | 7.48 | 7.34 | 7.09 |
| 10 | ≈ 5.49 | 5.97 | 6.42 | 6.82 | 7.11 | 7.30 | 7.37 | 7.49 | 7.96 | 8.63 | 8.43 | 8.34 | 8.18 | 7.91 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.432 |
| SC2 | 0 | 8 | 5.957 |
| SC3 | -18 | 7 | 4.932 |
| SC4 | -25 | 6 | 4.048 |
| SC5 | -34 | 6 | 3.748 |
| A | 1357 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1357 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.