EB-245AC7-B07 C
11.19 kW
Defrost: Electric
Product code: EB-240AC4-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,683 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 38.4 m² |
| Inner volume | 6.9 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 62 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-240AC4-B01 C | None |
|---|---|
| EB-240AC4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.60 | 4.71 | 4.81 | 4.89 | 4.92 | 4.91 | 4.87 | 4.93 | 5.24 | 5.66 | 5.52 | 5.47 | 5.41 | 5.29 |
| 5 | 5.73 | 5.96 | 6.17 | 6.36 | 6.48 | 6.55 | 6.58 | 6.65 | 7.05 | 7.63 | 7.43 | 7.36 | 7.25 | 7.08 |
| 6 | 6.77 | 7.11 | 7.39 | 7.67 | 7.86 | 7.98 | 8.03 | 8.14 | 8.66 | 9.40 | 9.21 | 9.13 | 9.01 | 8.83 |
| 7 | 7.68 | 8.17 | 8.61 | 9.00 | 9.26 | 9.43 | 9.51 | 9.65 | 10.25 | 11.15 | 10.91 | 10.81 | 10.67 | 10.42 |
| 8 | 8.52 | 9.16 | 9.75 | 10.26 | 10.63 | 10.88 | 10.98 | 11.14 | 11.85 | 12.88 | 12.62 | 12.51 | 12.34 | 12.06 |
| 9 | ≈ 9.27 | 10.08 | 10.83 | 11.40 | 11.89 | 12.23 | 12.44 | 12.66 | 13.47 | 14.66 | 14.38 | 14.26 | 14.06 | 13.72 |
| 10 | ≈ 9.95 | 10.93 | 11.72 | 12.56 | 13.18 | 13.62 | 13.90 | 14.17 | 15.09 | 16.44 | 16.15 | 16.02 | 15.80 | 15.42 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.152 |
| SC2 | 0 | 8 | 11.142 |
| SC3 | -18 | 7 | 9.116 |
| SC4 | -25 | 6 | 7.387 |
| SC5 | -34 | 6 | 6.851 |
| A | 1667 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E | 1335 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1667 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.