EB-430BE6-B01 C
11.77 kW
Defrost: Electric
Product code: EB-245AC6-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 10,218 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 27.7 m² |
| Inner volume | 6.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 71 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | E |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-245AC6-B01 C | None |
|---|---|
| EB-245AC6-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.94 | 4.88 | 4.83 | 4.79 | 4.72 | 4.63 | 4.53 | 4.57 | 4.81 | 5.17 | 4.99 | 4.93 | 4.84 | 4.71 |
| 5 | 6.52 | 6.56 | 6.59 | 6.62 | 6.58 | 6.49 | 6.37 | 6.41 | 6.78 | 7.29 | 7.04 | 6.96 | 6.84 | 6.67 |
| 6 | 7.92 | 8.09 | 8.25 | 8.41 | 8.49 | 8.51 | 8.41 | 8.45 | 8.94 | 9.62 | 9.28 | 9.16 | 8.98 | 8.71 |
| 7 | 9.23 | 9.50 | 9.73 | 9.97 | 10.11 | 10.18 | 10.18 | 10.28 | 10.91 | 11.82 | 11.52 | 11.40 | 11.23 | 10.96 |
| 8 | 10.41 | 10.83 | 11.21 | 11.55 | 11.76 | 11.86 | 11.89 | 12.01 | 12.74 | 13.81 | 13.46 | 13.32 | 13.11 | 12.77 |
| 9 | 11.52 | 12.10 | 12.63 | 13.10 | 13.40 | 13.57 | 13.64 | 13.77 | 14.61 | 15.85 | 15.44 | 15.27 | 15.03 | 14.62 |
| 10 | 12.55 | 13.32 | 14.01 | 14.61 | 15.02 | 15.22 | 15.35 | 15.52 | 16.48 | 17.88 | 17.45 | 17.26 | 16.98 | 16.51 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 17.451 |
| SC2 | 0 | 8 | 12.006 |
| SC3 | -18 | 7 | 10.035 |
| SC4 | -25 | 6 | 8.250 |
| SC5 | -34 | 6 | 7.967 |
| A | 1667 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E | 1335 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1667 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.