EB-240AC4-B01 C
11.14 kW
Defrost: Electric
Product code: EB-245AC7-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 10,405 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 24.2 m² |
| Inner volume | 6.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 71 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | E |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-245AC7-B01 C | None |
|---|---|
| EB-245AC7-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.47 | 4.38 | 4.31 | 4.25 | 4.17 | 4.08 | 3.99 | 4.00 | 4.21 | 4.52 | 4.36 | 4.30 | 4.22 | 4.10 |
| 5 | 5.96 | 5.95 | 5.94 | 5.93 | 5.87 | 5.77 | 5.65 | 5.66 | 5.98 | 6.43 | 6.20 | 6.12 | 6.01 | 5.82 |
| 6 | 7.38 | 7.50 | 7.62 | 7.70 | 7.70 | 7.63 | 7.51 | 7.52 | 7.95 | 8.55 | 8.22 | 8.11 | 7.95 | 7.71 |
| 7 | 8.58 | 8.79 | 9.00 | 9.20 | 9.31 | 9.35 | 9.34 | 9.43 | 10.00 | 10.83 | 10.46 | 10.32 | 10.11 | 9.77 |
| 8 | 9.78 | 10.10 | 10.41 | 10.66 | 10.83 | 10.92 | 10.94 | 11.03 | 11.70 | 12.68 | 12.35 | 12.22 | 12.03 | 11.72 |
| 9 | 10.86 | 11.32 | 11.75 | 12.14 | 12.38 | 12.52 | 12.55 | 12.67 | 13.44 | 14.57 | 14.20 | 14.05 | 13.82 | 13.45 |
| 10 | 11.87 | 12.49 | 13.06 | 13.57 | 13.91 | 14.11 | 14.20 | 14.33 | 15.20 | 16.46 | 16.07 | 15.90 | 15.64 | 15.21 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.067 |
| SC2 | 0 | 8 | 11.031 |
| SC3 | -18 | 7 | 9.252 |
| SC4 | -25 | 6 | 7.616 |
| SC5 | -34 | 6 | 7.417 |
| A | 1667 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E | 1335 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1667 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.