EB-230BC6-B01 C
4.47 kW
Defrost: Electric
Product code: EB-325AC6-B05 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,429 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 14.9 m² |
| Inner volume | 3.6 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 35 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 285 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 63.5 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EB-325AC6-B05 C | None |
|---|---|
| EB-325AC6-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.90 | 1.90 | 1.91 | 1.92 | 1.92 | 1.92 | 1.90 | 1.92 | 2.04 | 2.20 | 2.15 | 2.13 | 2.11 | 2.07 |
| 5 | 2.41 | 2.44 | 2.48 | 2.52 | 2.54 | 2.54 | 2.52 | 2.54 | 2.70 | 2.92 | 2.84 | 2.81 | 2.77 | 2.70 |
| 6 | 2.90 | 2.98 | 3.05 | 3.12 | 3.16 | 3.18 | 3.18 | 3.20 | 3.39 | 3.67 | 3.57 | 3.53 | 3.47 | 3.38 |
| 7 | 3.33 | 3.45 | 3.57 | 3.68 | 3.75 | 3.80 | 3.82 | 3.87 | 4.11 | 4.46 | 4.34 | 4.29 | 4.21 | 4.09 |
| 8 | 3.76 | 3.92 | 4.06 | 4.21 | 4.31 | 4.38 | 4.41 | 4.47 | 4.74 | 5.15 | 5.04 | 4.99 | 4.91 | 4.78 |
| 9 | 4.14 | 4.36 | 4.56 | 4.75 | 4.88 | 4.96 | 5.01 | 5.07 | 5.39 | 5.85 | 5.73 | 5.67 | 5.58 | 5.42 |
| 10 | 4.49 | 4.77 | 5.03 | 5.26 | 5.43 | 5.54 | 5.61 | 5.68 | 6.04 | 6.56 | 6.42 | 6.36 | 6.25 | 6.07 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.421 |
| SC2 | 0 | 8 | 4.466 |
| SC3 | -18 | 7 | 3.713 |
| SC4 | -25 | 6 | 3.052 |
| SC5 | -34 | 6 | 2.917 |
| A | 1617 mm |
|---|---|
| B | 520 mm |
| C | 363 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1295 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1617 mm |
|---|---|
| Width | 520 mm |
| Height | 363 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.