EB-230BC4-B05 C
4.69 kW
Defrost: Electric
Product code: EB-325BB4-B05 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,600 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 18.4 m² |
| Inner volume | 3.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 35 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 285 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 63.5 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EB-325BB4-B05 C | None |
|---|---|
| EB-325BB4-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.99 | 1.99 | 2.00 | 2.01 | 2.01 | 2.01 | 1.99 | 2.01 | 2.13 | 2.31 | 2.26 | 2.24 | 2.21 | 2.18 |
| 5 | 2.54 | 2.57 | 2.60 | 2.64 | 2.65 | 2.65 | 2.64 | 2.66 | 2.82 | 3.05 | 2.97 | 2.95 | 2.91 | 2.85 |
| 6 | 3.06 | 3.13 | 3.21 | 3.28 | 3.32 | 3.34 | 3.33 | 3.35 | 3.55 | 3.85 | 3.75 | 3.71 | 3.66 | 3.57 |
| 7 | 3.52 | 3.63 | 3.74 | 3.85 | 3.92 | 3.97 | 3.99 | 4.03 | 4.28 | 4.65 | 4.56 | 4.52 | 4.45 | 4.34 |
| 8 | 3.98 | 4.13 | 4.28 | 4.41 | 4.51 | 4.58 | 4.62 | 4.66 | 4.95 | 5.38 | 5.27 | 5.22 | 5.16 | 5.04 |
| 9 | 4.38 | 4.60 | 4.80 | 4.98 | 5.11 | 5.19 | 5.24 | 5.30 | 5.63 | 6.12 | 6.00 | 5.94 | 5.86 | 5.73 |
| 10 | 4.76 | 5.04 | 5.30 | 5.53 | 5.69 | 5.80 | 5.87 | 5.95 | 6.32 | 6.85 | 6.72 | 6.66 | 6.57 | 6.42 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.721 |
| SC2 | 0 | 8 | 4.663 |
| SC3 | -18 | 7 | 3.882 |
| SC4 | -25 | 6 | 3.208 |
| SC5 | -34 | 6 | 3.080 |
| A | 1857 mm |
|---|---|
| B | 520 mm |
| C | 363 mm |
| F | 345 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1857 mm |
|---|---|
| Width | 520 mm |
| Height | 363 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.