EB-330AB6-B05 C
4.55 kW
Defrost: None
Product code: EB-330AB7-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,228 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 11.7 m² |
| Inner volume | 3.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 39 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 186 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 69.4 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EB-330AB7-B01 C | None |
|---|---|
| EB-330AB7-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.85 | 1.80 | 1.77 | 1.75 | 1.73 | 1.70 | 1.67 | 1.68 | 1.77 | 1.91 | 1.85 | 1.83 | 1.81 | 1.76 |
| 5 | 2.45 | 2.43 | 2.41 | 2.40 | 2.38 | 2.34 | 2.31 | 2.31 | 2.44 | 2.63 | 2.55 | 2.52 | 2.48 | 2.42 |
| 6 | 3.06 | 3.06 | 3.07 | 3.09 | 3.08 | 3.05 | 3.01 | 3.01 | 3.18 | 3.43 | 3.31 | 3.27 | 3.21 | 3.13 |
| 7 | 3.64 | 3.69 | 3.74 | 3.79 | 3.81 | 3.80 | 3.77 | 3.77 | 3.98 | 4.30 | 4.15 | 4.10 | 4.02 | 3.90 |
| 8 | 4.15 | 4.23 | 4.33 | 4.42 | 4.48 | 4.52 | 4.53 | 4.56 | 4.82 | 5.21 | 5.05 | 4.98 | 4.89 | 4.74 |
| 9 | 4.65 | 4.78 | 4.90 | 5.02 | 5.11 | 5.16 | 5.18 | 5.22 | 5.54 | 6.01 | 5.87 | 5.81 | 5.73 | 5.58 |
| 10 | 5.11 | 5.30 | 5.47 | 5.63 | 5.75 | 5.81 | 5.85 | 5.90 | 6.26 | 6.79 | 6.64 | 6.57 | 6.47 | 6.30 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.636 |
| SC2 | 0 | 8 | 4.556 |
| SC3 | -18 | 7 | 3.802 |
| SC4 | -25 | 6 | 3.073 |
| SC5 | -34 | 6 | 3.064 |
| A | 1617 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1295 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1617 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.