EB-430BB4-B05 C
8.20 kW
Defrost: Electric
Product code: EB-330AE4-B01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,287 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 37.1 m² |
| Inner volume | 6.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 47 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 186 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 70.8 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø22 |
| EB-330AE4-B01 C | None |
|---|---|
| EB-330AE4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.45 | 3.58 | 3.70 | 3.80 | 3.86 | 3.87 | 3.85 | 3.94 | 4.19 | 4.56 | 4.44 | 4.41 | 4.35 | 4.28 |
| 5 | 4.22 | 4.44 | 4.64 | 4.82 | 4.93 | 4.99 | 4.99 | 5.08 | 5.40 | 5.86 | 5.70 | 5.63 | 5.53 | 5.37 |
| 6 | 4.88 | 5.20 | 5.49 | 5.74 | 5.91 | 6.01 | 6.03 | 6.14 | 6.53 | 7.10 | 6.90 | 6.82 | 6.70 | 6.49 |
| 7 | 5.55 | 5.96 | 6.34 | 6.67 | 6.90 | 7.02 | 7.07 | 7.19 | 7.64 | 8.29 | 8.06 | 7.96 | 7.80 | 7.53 |
| 8 | ≈ 6.10 | 6.62 | 7.11 | 7.54 | 7.85 | 8.03 | 8.12 | 8.22 | 8.73 | 9.47 | 9.22 | 9.10 | 8.92 | 8.59 |
| 9 | ≈ 6.60 | 7.24 | 7.84 | 8.38 | 8.77 | 8.97 | 9.10 | 9.27 | 9.85 | 10.68 | 10.41 | 10.27 | 10.06 | 9.67 |
| 10 | 7.04 | 7.80 | 8.53 | 9.11 | 9.59 | 9.92 | 10.11 | 10.31 | 10.96 | 11.89 | 11.60 | 11.45 | 11.21 | 10.77 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.604 |
| SC2 | 0 | 8 | 8.215 |
| SC3 | -18 | 7 | 6.769 |
| SC4 | -25 | 6 | 5.487 |
| SC5 | -34 | 6 | 4.955 |
| A | 1617 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1295 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø22 |
| Length | 1617 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.