EB-330BC4-B05 C
7.35 kW
Defrost: None
Product code: EB-330AE4-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 2,787 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 37.1 m² |
| Inner volume | 6.2 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 44 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EB-330AE4-B05 C | None |
|---|---|
| EB-330AE4-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.16 | 3.25 | 3.34 | 3.41 | 3.45 | 3.46 | 3.43 | 3.51 | 3.74 | 4.06 | 3.96 | 3.93 | 3.88 | 3.81 |
| 5 | 3.87 | 4.04 | 4.20 | 4.33 | 4.41 | 4.44 | 4.42 | 4.49 | 4.77 | 5.18 | 5.03 | 4.97 | 4.88 | 4.74 |
| 6 | 4.51 | 4.76 | 4.99 | 5.19 | 5.32 | 5.39 | 5.40 | 5.49 | 5.83 | 6.33 | 6.15 | 6.07 | 5.95 | 5.75 |
| 7 | 5.09 | 5.42 | 5.73 | 6.00 | 6.19 | 6.29 | 6.32 | 6.42 | 6.81 | 7.39 | 7.19 | 7.11 | 6.97 | 6.74 |
| 8 | 5.67 | 6.09 | 6.48 | 6.83 | 7.06 | 7.18 | 7.24 | 7.35 | 7.80 | 8.46 | 8.24 | 8.14 | 7.97 | 7.69 |
| 9 | ≈ 6.16 | 6.68 | 7.17 | 7.60 | 7.90 | 8.09 | 8.18 | 8.30 | 8.77 | 9.51 | 9.28 | 9.16 | 8.98 | 8.65 |
| 10 | ≈ 6.59 | 7.22 | 7.82 | 8.35 | 8.72 | 8.92 | 9.05 | 9.20 | 9.77 | 10.60 | 10.34 | 10.21 | 10.00 | 9.63 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.336 |
| SC2 | 0 | 8 | 7.349 |
| SC3 | -18 | 7 | 6.087 |
| SC4 | -25 | 6 | 4.986 |
| SC5 | -34 | 6 | 4.569 |
| A | 1617 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1295 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1617 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.