EB-330AE4-B05 C
7.35 kW
Defrost: None
Product code: EB-430BB6-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,858 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 21.3 m² |
| Inner volume | 5.3 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 55 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 70.7 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-430BB6-B01 C | None |
|---|---|
| EB-430BB6-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.06 | 3.00 | 2.97 | 2.95 | 2.92 | 2.89 | 2.85 | 2.86 | 3.03 | 3.27 | 3.18 | 3.14 | 3.10 | 3.03 |
| 5 | 4.01 | 3.98 | 3.98 | 3.98 | 3.96 | 3.93 | 3.88 | 3.89 | 4.12 | 4.44 | 4.31 | 4.26 | 4.20 | 4.10 |
| 6 | 4.95 | 4.98 | 5.03 | 5.07 | 5.08 | 5.06 | 5.02 | 5.02 | 5.31 | 5.73 | 5.56 | 5.49 | 5.40 | 5.26 |
| 7 | 5.81 | 5.91 | 6.03 | 6.14 | 6.22 | 6.24 | 6.21 | 6.23 | 6.59 | 7.12 | 6.91 | 6.83 | 6.71 | 6.52 |
| 8 | 6.59 | 6.76 | 6.93 | 7.10 | 7.21 | 7.28 | 7.31 | 7.37 | 7.82 | 8.49 | 8.30 | 8.22 | 8.09 | 7.87 |
| 9 | 7.38 | 7.61 | 7.84 | 8.06 | 8.20 | 8.30 | 8.35 | 8.42 | 8.94 | 9.70 | 9.49 | 9.40 | 9.27 | 9.06 |
| 10 | 8.08 | 8.41 | 8.72 | 9.00 | 9.20 | 9.33 | 9.40 | 9.49 | 10.07 | 10.94 | 10.71 | 10.61 | 10.46 | 10.21 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.707 |
| SC2 | 0 | 8 | 7.367 |
| SC3 | -18 | 7 | 6.179 |
| SC4 | -25 | 6 | 5.025 |
| SC5 | -34 | 6 | 4.962 |
| A | 2357 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2357 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.